Thermal (T- and TA-Line)
TA45 2 pole Rocker
https://www.schurter.com /PG17_20
Circuit Breaker for Equipment thermal, 2 pole, Rocker actuation
Basic type
With auxiliary contact
With undervoltage protection
See below:
Approvals and Compliances
Description
Applications
- Thermal circuit breaker
- 1 or 2 pole thermal overload protection
- Positively trip-free release
- High configurability
- Power tools
- Industrial appliances
- Power supplies
- Equipment for construction
- Cleaning equipment
- Rocker non-illuminated or illuminated
- Snap-in version
- Quick connect terminal 6.3 x 0.8 mm or screw clamp terminal M3.5 x
6 mm (lineside P1, P2)
References
Weblinks
pdf data sheet, html datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
Rated Voltage AC
Rated Voltage DC
240 VAC
60 VDC
Overload
AC: min. 40trips
@ 6 x Ir
DC: min. 40trips
@ 4 x Ir
-10°C to 55°C
Rated current range AC
Conditional short circuit capa- IEC 60934: PC1, AC 240 V: 1 kA
city Inc
0.05 - 20 A
Allowable Operation Temp.
Storage Temperature
Vibration Resistance
-10°C to 55°C
Short circuit capacity Icn
IEC 60934:
At In < 3 A/ 240 VAC: 10xIn (max. 3
cycles)
At In ≥ 3 A/ 240 VAC: 300A (max. 3
cycles)
At In < 3 A/ 60 VDC: 10xIn (max. 3
cycles)
At In ≥ 3 A/ 48 VDC: 120A (max. 3
cycles)
0.ꢀ5 mm @ 5 - 60 Hꢁ
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hꢁ
acc. to IEC 60068-2-6, test Fc
30 G / 18ms
acc. to IEC 60068-2-2ꢀ, test Ea
Thermal
Shock Resistance
Tripping Type
Actuation Type
Weight
Rocker
30 - 50g
Degree of Protection
front side IP40 acc. to IEC 60529
With factory mounted protection cover
IP54
Dielectric Strength
Insulation Resistance
Lifetime
4kVAC
500VDC > 100 MΩ
mechanical: 50'000switching cycles
AC: 1 x Ir:
50'000switching cycles
DC: 1 x Ir:
50'000switching cycles
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national
and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF
16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree-
ments by SCHURTER.