MODEL: R7D  
DATA CONVERSION  
I 0 – 100% DATA CONVERSION  
Analog input data is converted into digital representations of 0 – 100% proportional to each scaled range. The converted %  
values are multiplied by 100 and expressed in 16 bits.  
Overrange input is possible from -15 to +115% of the nominal range. When the signal exceeds the limit, the data is fixed at  
-15% or +115% respectively. Negative value is represented in 2ʼs complements.  
• Input Range 0 – 5 V DC  
Converted Data, Decimal  
Converted Data, Hex  
Input Value  
≤ -0.75 V  
0 V  
Input %  
-15%  
0%  
-1500  
0
FA24  
0
10000  
11500  
5 V  
100%  
115%  
2710  
2CEC  
≥ 5.75 V  
11500 (2CEC)  
10000 (2710)  
-0.75  
0
-1500 (FA24)  
5.0  
5.75  
(V)  
Analog output is converted in the reverse order of the input data. The output range 0 – 5 V DC is expressed as 10000 at  
5.0 V (100%) and 0 at 0 V (0%).  
I ENGINEERING UNIT CONVERSION  
Engineering unit value °C or K is multiplied by 10 and expressed in 16 bits. °F data is represented in engineering unit  
value, without multiplication. Engineering unit value A is multiplied by 100 or 1000, expressed in 16 bits. Negative value  
is represented in 2ʼs complements.  
• Input TYPE K Thermocouple  
Converted Data, Decimal  
Converted Data, Hex  
Input Value  
≤ -272°C  
-150°C  
-2720  
-1500  
13700  
14720  
F560  
FA24  
3584  
3980  
1370°C  
≥ 1472°C  
14720 (3980)  
13700 (3584)  
-272 -150  
1370  
1472  
(°C)  
-1500 (FA24)  
-2720 (F560)  
COUNT VALUE  
The count value is 32-bit data. It is divided in 2 words of 16 bits represented with 2 addresses.The lower address is  
allocated in the lower word (LSB) and the upper address in the upper word (MSB). The count value is 0 - 4 294 967 295.  
The maximum count value available is 1 000 - 4 294 967 295. In case of overflow, the vaule is reset to 0 or 1  
(configurable) from which the count will restart. The preset of the count value is also available. Use the R7CON or  
commands for the configuration.  
R7D SPECIFICATIONS  
ES-7802 Rev.21 Page 5/38  
http://www.m-system.co.jp/  

与R7D-YB2A/Q相关器件

型号 品牌 描述 获取价格 数据表
R7D-YB2A/UL MSYSTEM Remote I/O R7 Series DeviceNet I/O MODULE

获取价格

R7D-YS2 MSYSTEM Remote I/O R7 Series DeviceNet I/O MODULE

获取价格

R7D-YS2/Q MSYSTEM Remote I/O R7 Series DeviceNet I/O MODULE

获取价格

R7D-YS2/UL MSYSTEM Remote I/O R7 Series DeviceNet I/O MODULE

获取价格

R7D-YS2A MSYSTEM Remote I/O R7 Series DeviceNet I/O MODULE

获取价格

R7D-YS2A/Q MSYSTEM Remote I/O R7 Series DeviceNet I/O MODULE

获取价格