MODEL: R7D
DATA CONVERSION
I 0 – 100% DATA CONVERSION
Analog input data is converted into digital representations of 0 – 100% proportional to each scaled range. The converted %
values are multiplied by 100 and expressed in 16 bits.
Overrange input is possible from -15 to +115% of the nominal range. When the signal exceeds the limit, the data is fixed at
-15% or +115% respectively. Negative value is represented in 2ʼs complements.
• Input Range 0 – 5 V DC
Converted Data, Decimal
Converted Data, Hex
Input Value
≤ -0.75 V
0 V
Input %
-15%
0%
-1500
0
FA24
0
10000
11500
5 V
100%
115%
2710
2CEC
≥ 5.75 V
11500 (2CEC)
10000 (2710)
-0.75
0
-1500 (FA24)
5.0
5.75
(V)
Analog output is converted in the reverse order of the input data. The output range 0 – 5 V DC is expressed as 10000 at
5.0 V (100%) and 0 at 0 V (0%).
I ENGINEERING UNIT CONVERSION
Engineering unit value °C or K is multiplied by 10 and expressed in 16 bits. °F data is represented in engineering unit
value, without multiplication. Engineering unit value A is multiplied by 100 or 1000, expressed in 16 bits. Negative value
is represented in 2ʼs complements.
• Input TYPE K Thermocouple
Converted Data, Decimal
Converted Data, Hex
Input Value
≤ -272°C
-150°C
-2720
-1500
13700
14720
F560
FA24
3584
3980
1370°C
≥ 1472°C
14720 (3980)
13700 (3584)
-272 -150
1370
1472
(°C)
-1500 (FA24)
-2720 (F560)
■ COUNT VALUE
The count value is 32-bit data. It is divided in 2 words of 16 bits represented with 2 addresses.The lower address is
allocated in the lower word (LSB) and the upper address in the upper word (MSB). The count value is 0 - 4 294 967 295.
The maximum count value available is 1 000 - 4 294 967 295. In case of overflow, the vaule is reset to 0 or 1
(configurable) from which the count will restart. The preset of the count value is also available. Use the R7CON or
commands for the configuration.