RxxPxx/R
DC/DC Converter
Specifications (measured @ Ta= 25°C, nom. Vin, full load and after warm-up unless otherwise stated)
Series
Deviation vs. Load
RxxP05S/R6.4 and RxxP09S/R8
RxxP05D/R6.4 and RxxP09D/R8
25
20
15
10
5
25
20
15
10
5
0
0
-5
-5
R05P05S/R6.4
R12P05S/R6.4
R24P05S/R6.4
R05P05D/R6.4
R12P05D/R6.4
R24P05D/R6.4
-10
-15
-10
-15
0
10 20 30 40 50 60 70 80 90 100
0
10 20 30 40 50 60 70 80 90 100
ꢅꢆtpꢆt ꢇoꢁꢈ ꢂꢃꢄ
ꢅꢆtpꢆt ꢇoꢁꢈ ꢂꢃꢄ
PROTECTIONS
Parameter
Type
Value
without Suffix “/P”
with Suffix “/P”
1 second
continuous
Short Circuit Protection (SCP)
“/R6.4”
“/R8”
6.4kVDC
8kVDC
tested for 1 second
rated for 1 minute
Isolation Voltage(7)
I/P to O/P
“/R6.4”
“/R8”
3.2kVAC/60Hz
4kVAC/60Hz
15GΩ min.
Isolation Resistance
Isolation Capacitance
Leakage Current
4.0pF min. / 10pF max.
<0.01µA max.
reinforced
Insulation Grade
Means of Protection
34Vrms
2MOPP
clearance/creepage
clearance/creepage
>4.8mm
Internal
External
>4.8mm
Notes:
Note7: For repeat Hi-Pot testing, reduce the time and/or the test voltage
ENVIRONMENTAL
Parameter
Operating Temperature Range
Maximum Case Temperature
Operating Altitude
Condition
Value
-40°C to +85°C
+105°C
without derating @ free air convection (see graph)
3000m
Operating Humidity
non-condensing
95ꢀ RH max.
PD2
Pollution Degree
+25°C
according to MIL-HDBK-217F, G.B.
+85°C
2974 x 103 hours
728 x 103 hours
MTBF
continued on next page
REV.: 6/2020
www.recom-power.com
ECO-3