Monitoring Relays
1-Phase True RMS AC Over/Under Voltage
Types DUB02, PUB02
• TRMS AC over/under voltage monitoring
relays
• Measuring if power supply is within set limits
• Measure on own power supply
• Measuring ranges: 24, 115, 230 VAC
• Power ON delay 1 or 6 s selectable by DIP-switch
• Separately adjustable upper/lower level on relative scale
• Adjustable delay on alarm or on recovery (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DUB02) or plug-in module (PUB02)
• 22.5 mm Euronorm housing (DUB02)
DUB02
PUB02
or 36 mm plug-in module (PUB02)
• LED indication for relay, alarm and power supply ON
Product Description
Ordering Key
DUB 02 C T23
DUB02 and PUB02 are pre- even after the end of the Housing
cise TRMS AC window volt- alarm condition. Inhibit func- Function
age monitoring relays.
tion can be used to avoid Type
The relays monitor their own relay operation when not Item number
power supply which is select- desired (maintenance, transi- Output
able by DIP-switch (24, 115 or tions).
Power supply
230 VAC).
The LED's indicate the state
The advantage of using the of the alarm and the output
latch function is that the relay.
relay can be kept energized
Type Selection
Mounting
Output
Supply: 24, 115, 230 VAC
DIN-rail
Plug-in
SPDT
SPDT
DUB 02 C T23
PUB 02 C T23
Input Specifications
Output Specifications
Input
Output
SPDT relay
250 VAC
Own power supply DUB02:
PUB02:
A1, A2 (24, 115, 230 VAC)
2, 10 (24, 115, 230 VAC)
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
µ
AC 1
DC 12
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Measuring ranges
Selectable by DIP-switch
24 VAC
Upper level
Lower level
-5% to +20% -20% to +5%
22.8 to 28.8 V 19.2 to 25.2 V
Small inductive loads AC 15
DC 13
115 VAC
230 VAC
109 to 138 V
218 to 275 V
92 to 121 V
184 to 242 V
Mechanical life
Electrical life
≥ 30 x 106 operations
≥ 105 operations
Contact input
DUB02
PUB02
Disabled
Enabled
Pulse width
(at 8 A, 250 V, cos ϕ = 1)
Terminals Z1, Z2
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
Operating frequency
Dielectric strength
Dielectric voltage
≤ 7200 operations/h
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Hysteresis
~ 2% of set value - fixed
Specifications are subject to change without notice (21.10.00)
1