HO-NP/SP33-1000 SERIES
Insulation coordination
Parameter
Symbol
Unit
Value
Comment
Rms voltage for AC isolation test 50/60Hz/1 min
Ud
kV
4.3
Impulse withstand voltage 1.2/50 µs
Partial discharge extinction rms voltage @ 10 pC
Clearance (pri. - sec.)
ÛW
Ue
kV
V
8
1650
8
dCI
mm
Shortest distance through air
Shortest path along device
body
Creepage distance (pri. - sec.)
dCp
mm
8
V0 according
to UL 94
Case material
Comparative tracking index
CTI
V
600
Reinforced insulation, non
uniform field according to
EN 50178
600 V
CAT III PD2
Application example
Application example
Application example
-
-
Reinforced insulation, non
uniform field according to
IEC 61010
300 V
CAT III PD2
-
-
-
-
Simple insulation, non uniform
field according to
EN 50178, IEC 61010
1000 V
CAT III PD2
Environmental and mechanical characteristics
Parameter
Ambient operating temperature
Symbol
Unit
°C
°C
°C
g
Min
-40
-40
Typ
Max
105
105
105
Comment
TA
TS
Ambient storage temperature
Surrounding temperature according to UL 508
Mass
m
5
Page 3/15
17September2013/Version 2 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com