EtherTRAK®-2 Ethernet I/O Module Specifications
SPECIFICATIONS
Discrete Input Channels
•
•
•
•
Voltage range: 10–30 VDC or 60–140 VAC
Input isolation: 150 volts (16 channel modules only)
Input resistance: 10 Kohms
General I/O Performance
• Power supply voltage: 10-30 VDC
Slow response (software configurable): 25 mS (20 Hz. maximum
counting rate)
Fastest response (software configurable): 1 mS (400 Hz. maximum
counting rate)
• Input current requirement: 100 mA @ 24 VDC typical with no loads
• PoE power (EB modules only): 10 watts at 60°C for user loads
• De-rate: up to 5 watts at 75°C
•
• I/O: 512 discrete inputs and outputs plus 256 analog input and
output registers
•
•
•
Special fast counting rate: up to 50 KHz on channels 1 and 2
Count up: pulse timing and pulse rate 16 or 32-bit reporting
Refer to user manual for additional specifications
• Unique station addresses: 16,000+ (Sixnet or 247 Modbus)
Ethernet Performance
Discrete Output Channels
• Ethernet ports: 10/100BaseTx (auto-detecting)
• Connection: RJ45 (auto-crossover)
• Output voltage range: 10-30 VDC or 10-30VDC/AC
• Maximum output power: up to 1A per channel
• Short circuit protection: self-reset fuses (trip above 1.5 Amp)
• Input isolation: 150 volts (16 channel modules only)
• All channels scan rate: 1 mS
• Isolation: 1500 volts RMS 1 minute (60 Hz.)
• Message response time: <1 mS per message
• Diagnostic LEDs: solid indicates link, blinking indicates activity
• Protocol support: TCP/IP, ARP, UDP, ICMP, DHCP, HTTP, Modbus
UDP/TCP slave mode, Modbus UDP master mode, Sixnet UDR UDP/
TCP slave mode, Sixnet UDR UDP master mode
• Refer to user manual for additional specifications
Web Interface
• Real-Time Ring: 5ms per hop recovery time
• Secure web access with password protection for multiple users
• 1 simultaneous user
• Independent networks: 1 or 2 with unique MAC and IP addres
• 750K memory for user pages (more with special order)
Serial Ports
Environmental
• RS-485 port: screw terminals (485+, 485-, GND; 2-wire half-
duplex, not isolated)
• Operating temperature: -40 to 75°C (-40 to 85°C storage)
• Humidity: 5 to 95% RH (non-condensing; optional conformal
coating)
• RS-485 networking: up to 32 (full load) stations
• RS-485 distance: up to 0.5 miles (baud-rate dependent)
• Baud rates: from 300 to 57,600 baud
• Flammability: UL 94V-0 materials
• Vibration: IEC60068-2-6
• Protocols: master and slave; Sixnet and Modbus RTU/ASCII
• Diagnostic LEDs: transmit (TD) and receive (RD)
• Shock: IEC60068-2-27
Analog Output Channels
Standards Compliance
• Analog output range: 4-20 mA
• Electrical safety : UL 508, CSA C22.2/142; EN61010-1; CE
• EMI emissions: FCC part 15, ICES-003, Class A; EN55022;
IEC6100-6-4; CE
• D/A resolution: 16 bits (less than 1 uA)
• Full scale accuracy: +/-0.02% (at 20°C)
• Span and offset temperature: +/- 50 ppm per °C
• Load resistance (@ 24 V): 0-750 Ohms
• Current limiting short circuit protection
• Refer to user manual for additional specifications
• EMC immunity : IEC61000-6-2 (EN61000-4-2,3,4, 5, 6, 8); CE
• Hazardous locations: Class 1, Div 2, Groups A, B, C, D; ISA12.12.01;
CSA C22.2/213; ATEX (Zone 2) IEC60079-0,-15
• Marine and offshore: tested and/or verified to meet various
standards such as ABS, DNV No. 2.4, and Lloyds
Analog Input Channels
Physical
• Input range: 4-20mA, 0-10VDC, RTD, thermocouple and 250mV
• A/D resolution: 16 bits (0.003%); 10 bits (1mS fast option)
• Input impedance (resistance): 100 ohms or 200 Kohms
• Fuses: self-resetting short circuit protection (4-20 mA inputs)
• DMRR (differential mode): 66 db at 50/60 Hz
• Mounting: DIN rail (EN50022), direct to panel or flat panel
• Packaging: impact resistant Lexan® polycarbonate
• Dimensions (module and base): 5.5”L x 3.5”W x 5.1”H (14cm x
8.9cm x 13cm)
• Update time: from 880 mS to 1 mS (depending configuration)
Warranty
°
• Temperature accuracy: typical uncalibrated +/-0.5 C
•
RTD type: 100 Ohm platinum
• RTD alpha: 0.00385 or 0.00392
RTD connections: 2 or 3-wire
• 2 years on design and manufacturing defects
•
°
RTD input range: -200 to 850 C
•
All specifications are subject to change. Contact Sixnet to learn more.
• Refer to user manual for additional specifications