Filters for power lines
B84299*B001
B84299*E001
16 to 100 A, 100 dB from 150 kHz
General technical data (continued)
Power dissipation
PD
See characteristics
At rated current IR
Capacitive reactive current/line Ireactive See characteristics
At 400/230 V and 50 Hz (typical
value)
Max. permissible harmonic
distortion (THD)
8
%
To EN 50160
Permissible ambient
temperature
TA
ꢁ25/+40
°C
Climatic category
(EN 60068-1)
25/085/56
ꢁ25 °C/+85 °C/56 days damp
heat test
Mechanical version
C
D
Cable glands at both ends or
flexible connector fitting
Direct connection to shielding
wall
Characteristics and ordering codes
IR
Mechanical Rmax
version
PD
W
Ireactive Dimensional Page Approx. Ordering code
drawing
weight
kg
A
mΩ
A
2-line filters
C
D
C
D
C
D
C
D
0.7
0.7
1.0
1.0
1.0
1.0
1.0
1.0
6
7
8
9
10
11
12
13
B84299C2160B001
B84299D2160B001
B84299C2320B001
B84299D2320B001
B84299C1630B001
B84299D1630B001
B84299C1101B001
B84299D1101B001
16
16
32
32
63
63
100
100
< 25
< 25
< 20
< 20
< 3.0
< 3.0
< 1.5
< 1.5
< 15
< 15
< 40
< 40
< 25
< 25
< 30
< 30
1
2
3
4
5
6
7
8
8
8
15
15
18
18
18
18
4-line filters
C
D
C
D
C
D
C
D
0.7
0.7
1.0
1.0
1.0
1.0
1.0
1.0
14
15
16
17
10
11
12
13
B84299C2160E001
B84299D2160E001
B84299C2320E001
B84299D2320E001
B84299C1630E001
B84299D1630E001
B84299C1101E001
B84299D1101E001
16
16
32
32
63
63
100
100
< 50
< 50
< 20
< 20
< 3.0
< 3.0
< 1.5
< 1.5
< 30
< 30
< 40
< 40
< 35
< 35
< 45
< 45
9
10
11
12
5
6
7
8
16
16
20
20
20
20
20
20
5