3-line filters
B84143G*R110
for converters and power electronics
Technical data and measuring conditions
Rated voltage VR
520/300 V AC (50/60 Hz)
Rated voltage for IT mains supply Filters 8 A: Up to 480/275 V AC (50/60 Hz)
Filters 20 A ... 220 A: Up to 460/265 V AC (50/60 Hz)
See also chapter "General technical information", section 7.
Rated current IR
Test voltage Vtest
Referred to 40 °C rated temperature
2250 V DC, 2 s (line/line)
2720 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 ꢀ IR for 3 min per hour or
2.5 ꢀ IR for 30 s per hour
Leakage current lLK
Climatic category (IEC 60068-1)
Approvals
At VR and 50 Hz
25/100/21 (ꢁ25 °C/+100 °C/21 days damp heat test)
IEC 60939, UL 1283 for 480 V AC
Characteristics and ordering codes
Approvals
480 V
Terminal cross section
Line side: Load side:
IR
ILK
Rtyp
Approx. weight Ordering code
terminal
blocks
mm2
litz wires
mm2
A
mA
mΩ kg
VR = 520/300 V AC
8
20
25
36
50 16
66 25
4
4
4
6
1.5
2.5
2.5
6.0
10
16
25
35
35
1.64
1.64
1.64
5.0
5.0
5.0
5.0
5.0
5.0
5.0
40
10
10
1.3
B84143G0008R110 ×
×
×
ꢁ
×
×
×
×
×
×
×
1.3
1.3
2.8
3.3
4.4
4.9
7.5
8.0
B84143G0020R110 ×
B84143G0025R110 ×
B84143G0036R110 ×
B84143G0050R110 ×
B84143G0066R110 ×
B84143G0090R110 ×
B84143G0120R110 ×
B84143G0150R110 ×
B84143G0220R110 ×
5.2
2.4
1.8
1.2
1.0
0.7
90 25
120 50
150 50
220 95
70
0.4 11.5
× = Approval granted
Please read Cautions and warnings and
Important notes at the end of this document.