Dimensions AHR-B5 (in mm. 1 mm = 0.0394 inch)
25
20
174
9.10
104
50.50
54.10
22. 28
15
20.34
35
5.50
55
110
150
Connections
Mechanical characteristics
· General tolerance
· Primary aperture
· Busbar fastening
± 1 mm
· Wires up to 2 mm Æ
104 x 40 mm
· Female connector provided (screw terminals)
1 hole Æ 5.5 mm &
2 slots 5.5 x 30 mm
4 holes Æ 3.2 mm
15 x 150 mm
Output Connector
AHR
1(Vcc) 2(NC) 3(Vout) 4(GND)
Panel mounting
Distance between hole axes
Remarks
24 VDC Power
· The return busbar and primary conductor elbow must be
located at a minimum distance of 2.5 x the window length
away from the transducer case.
(+)
(-)
· The temperature of the primary busbar can not exceed
90°C.
· Dynamic performances are the best with a primary busbar
completely filling the primary aperture.
(-)
(+)
Load
(Controller, meter etc)
· This is a standard model. For different versions (supply
voltages, different outputs, bidirectional measurements...),
please contact us.
+24VDC
OUT
Is
Ip
GND
Page 3/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
061128/6
www.lem.com