A-Series Circuit Breaker - General Specifications
2
Electrical
Maximum Voltage
Current Ratings
Mechanical
277VAC 50/60 Hz, 80VDC
Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50,
5.00, 7.50, 10.0, 15.0, 20.0, 25.0,
30.0, 35.0, 40.0, 50.0. Other ratings
available - consult ordering
scheme.
Endurance
10,000 ON-OFF operations @ 6 per
minute; with rated Current & Voltage.
All A-Series Circuit Breakers will trip
on overload, even when the actuator
is forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when
an overload causes the circuit
breaker to trip. When mid-trip
Trip Free
Trip Indication
Standard Voltage Coils DC-6V, 12V; AC-120V, Other ratings
available, consult ordering scheme.
Auxiliary Switch Rating SPDT; 10.1 A - 250VAC,
1.0 A-65VDC/0.5 A - 80 VDC,
handle is specified, the handle
moves to the mid position on
0.1A - 125VAC (with gold contacts).
Minimum: 100 Megohms at 500
VDC
electrical trip of the circuit breaker.
When mid-trip handle with alarm
switch is specified, the handle
moves to the mid position & the
alarm switch actuates when the
circuit breaker is electrically tripped.
Insulation Resistance
Dielectric Strength
UL, CSA - 1500V 60 Hz for one
minute between all electrically
isolated terminals. A-Series rocker
circuit breakers comply with the
8mm spacing & 3750V dielectric
requirements from hazardous
voltage to operator accessible
surfaces per EN 60950 and VDE
0805.
Physical
Number of Poles
1 - 6 Poles (handle) and 1-3 poles
(rocker) at 30 Amps or less. 1 and 2
poles at 31 Amps thru 50 Amps.
Internal Circuit Config. Series, (with or without auxiliary
switch), Shunt and Relay with current
or voltage trip coils, Dual Coil,
Resistance, Impedance Values from Line to Load Terminal
- based on Series Trip Circuit
Breaker.
Switch Only with or without auxiliary
switch.
Approximately 65 grams/pole.
(Approximately 2.32 ounces/pole)
Housing - Black; Actuator- See
Ordering Scheme.
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Weight
Standard Colors
CURRENT
(AMPS)
TOLERANCE
(%)
0.10 - 5.0
5.1 - 20.0
20.1 - 50.0
15
25
35
Environmental
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short curves
tested @ 90% of rated current.
Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz,
at rated current per Method 204C,
Test Condition A. Instantaneous and
ultrashort curves tested at 90% of
rated current.
Vibration
Pulse Tolerance Curves
Moisture Resistance
Method 106D; ten 24-hour cycles @
+ 25°C to +65°C, 80-98% RH.56
days @ +85°C, 85% RH.
Salt Spray
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C to
+25°C).
Thermal Shock
Operating Temperature -40° C to +85° C
*Manufacturer reserves the right to change product specification without prior notice.