https://www.phoenixcontact.com/us/products/3210193
Disconnect terminal block - PT 2,5-TWIN-TGB - 3210193
Technical data
General
Nominal cross section
Color
2.5 mm²
gray
Insulating material
PA
Flammability rating according to UL 94
Area of application
V0
Railway industry
Machine building
Plant engineering
Rated surge voltage
6 kV
Degree of pollution
3
Overvoltage category
III
Insulating material group
Maximum load current
I
16 A (with 4 mm² conductor cross section)
Nominal current IN
16 A
Nominal voltage UN
400 V
Open side panel
Yes
Shock protection test specification
Back of the hand protection
Finger protection
DIN EN 50274 (VDE 0660-514):2002-11
guaranteed
guaranteed
Test passed
7.3 kV
Result of surge voltage test
Surge voltage test setpoint
Result of power-frequency withstand voltage test
Power frequency withstand voltage setpoint
Test passed
1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor
connection)
Test passed
Result of bending test
Test passed
10 rpm
Bending test rotation speed
Bending test turns
135
Bending test conductor cross section/weight
0.14 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
Test passed
0.14 mm²
10 N
Tensile test result
Conductor cross section tensile test
Tractive force setpoint
Conductor cross section tensile test
Tractive force setpoint
2.5 mm²
50 N
Conductor cross section tensile test
Tractive force setpoint
4 mm²
60 N
09/06/2016 Page 2 / 28