PRODUCT SPECIFICATION
Certificato N. 9125.FLA2
ISO 9001
NETWORK CABLE SERIES 155431-1xxx
ProfiBUS DP 150Ω - 2x22AWG - shield - PUR jacket
Style 20233 (80°C / 300V)
1. CONSTRUCTION DATA
1.1 CONDUCTOR:
Bare copper strand; according to EN 13602 - ETP1; stranding according to DIN VDE 0295, EN60228 Class 6
Stranded lay compliant with UL 758.
1.2 WIRE STRUCTURE:
Diameter of
Stranding
(nbr of wires x wire
diameter in mm)
Max Resistance
Ref. std. IEC 60344
(Ω/km)
Nominal section
AWG
stranded core
(mm²)
(mm)
0.34
22
19x0.15
0.75
60.0
1.3 INSULATION:
Foam PE; Max Insulation resistance >200 MΩxkm (IEC60189-1&IEC60885-1 or EN50289-1-4); according to UL758,
cores colors refer to Annex #1
1.4 INSULATION DIAMETER
Nominal section
Nominal Ø
Nominal thickness
(mm²)
(mm)
(mm)
0.34
2.75
1.00
1.5 ASSEMBLY:
Cores stranded together, with two fillers between cores
1.6 TAPE SHIELD:
Aluminum/PET tape (Al face outside), nominal optical coverage 100%.
1.7 BRAID SHIELD:
Tin copper wire, nominal optical coverage 80%.
1.8 TAPE:
Over braid shield
1.9 JACKET:
Polyurethane (PUR, TPU), ether base, Halogen free, nominal hardness 90 Shore A; Silicone, Pb,Cd,Hg & FCKW free;
according to UL758.
For overall diameter, jacket color refer to Annex #1.
REVISION HISTORY
ECR/ECN INFORMATION:
TITLE:
Page
of
Rev.A 04/11/2015 RELEASED
ProfiBUS DP 150Ω – PUR jacket
1
3
Created/Revised by:
Checked by:
A. Defendi
Approved by:
C. Lerose
Template: TDS REV.0 22/07/2015
D1oc5um5e4n3t N1u1m0b0er4: PS P1E A
M. Arrigoni
THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO MOLEX ELECTRONIC TECHNOLOGIES, LLC AND SHOULD NOT BE USED WITHOUT WRITTEN PERMISSION