MODEL: 10JF
High-density Signal Conditioners 10-RACK
[2] OUTPUT 1
Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
2-input MATH FUNCTION MODULE
(field-programmable)
6: 1 – 5 V DC (Load resistance 500 Ω min.)
Functions & Features
• Providing temperature or pressure compensation for a gas
flow, and other arithmetic operations
• Microprocessor based
[3] OUTPUT 2
0: None
• Equation and parameters selectable on site via hand-held
programmer PU-2x
Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
• Loop testing
• Optional second channel output available at the front
terminals and at the Standard Rack connector
POWER INPUT
DC Power
R: 24 V DC
Typical Applications
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Various flowmeters
• Adding two flows
[4] OPTIONS (multiple selections)
Equation (Refer to the EQUATION table)
/1: Temperature compensation for DP flowmeter (ideal gas)
/2: Pressure compensation for DP flowmeter (ideal gas)
/3: Addition/subtraction
• Ratio calculation
• Calculating average temperature
/4: Multiplication
/5: Division
Other Options
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
MODEL: 10JF-[1][2][3]-R[4]
/C03: Rubber coating
ORDERING INFORMATION
• Code number: 10JF-[1][2][3]-R[4]
Specify a code from below for each of [1] through [4].
(e.g. 10JF-6A6-R/3/Q)
• Parameters
Use Ordering Information Sheet (No. ESU 1980). Default
setting will be used if not otherwise specified.
(K0
= 1, K
1
= 1, K
2
= 1, A
0
= 0 %, A
1
= 0 %, A = 0 %)
2
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT
Current
A: 4 – 20 mA DC (Input resistance 100 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
10JF SPECIFICATIONS
ES-0880 Rev.11 Page 1/3
http://www.m-system.co.jp/