Technical data
NOTE: Data apply where T = 25°C and U = 24 V DC.
A
B
Operating data
Nominal voltage U
24 V DC (18 V DC ... 32 V DC)
B
Nominal current I
Depending on product version selected:
N
Fixed current strengths: 0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A, 12 A
Closed-circuit current I
When ON: Typically 20 mA ... 30 mA, depending on signal output
0
Shutdown
Shutdown times
Typical behavior
Refer to the time/current characteristic curve (see page 8)
3 s where I
> 1.1 x I
load
N
100 ms ... 3 s where I
> 1.8 x I (or 1.5 x I /1.3 x I )
N N N
load
EC-E4: Pin 11/12
EC-E1: Pin 13/14
EC-E: SF 23, RE 22
Individual signaling (N/C contact)
Individual signaling (N/O contact)
RE reset input, SF status output
Status indicators
Operating state signaling
–
–
–
–
Multi-color LED
SF status output (option)
Floating signal contact (F alarm output) (option)
On/off setting for switch S1
Multi-color LED
Green = Device switched on (S1 = ON) or load circuit/Power MOSFET forced
to trip
Orange = Overload or short circuit leading to electronic shutdown
Red = Device shut down electronically, load circuit/Power MOSFET switched
off, undervoltage (U < 8 V) or after switch-on up to end of switch-on delay
B
time
OFF: Manually switched off (S1 = OFF) or device voltage is disconnected
Load circuit
Load output
Power MOSFET switching output (positive switching)
Overload shutdown (OL)
Typically 1.1 x I (1.05 ... 1.35 x I )
N N
Short-circuit current I
Active current limitation (see page 5)
K
Temperature shutdown
Undervoltage monitoring for load output after each switch-on procedure
Switch-on delay t
Internal temperature monitoring with electronic shutdown
With hysteresis, no reset required: Load "OFF" at U < 8 V
B
Typically 0.5 s after reset and after U applied
B
Start
Load circuit shutdown
Free running circuit
Parallel connection of multiple load outputs
Electronic shutdown after overload/short circuit
External free-wheeling diode recommended for inductive load
Not permitted
F alarm output, signal contact (for EC-E1 and EC-E4 only)
Electrical data
Floating signal contact
30 V DC/0.5 A maximum, 10 V/10 mA minimum
Normal state, LED lights up green
OFF state, LED off
U
–
–
is present, switch S1 is set to ON, and no overloads or short circuits occur
Device switched off (switch S1 set to OFF)
B
Operating voltage U is not present
B
103906_en_01
PHOENIX CONTACT