(1/2)
Conformity to RoHS Directive
EMC Filters for AC Power Line
For Triple-phase, Large-size Box Cased(Square Wire Winding Type) ZRCF Series
FEATURES
SAFETY STANDARDS
Standard and standard No.
• The ZRCF series employ a highly efficient thermal design, which
ensures high current handling capacity in a compact package
with superior EMC suppression characteristics.
• They are highly effective at preventing both the radiation and
penetration of EMC noise. The parts are, therefore, highly
immune to externally generated noise and do not, themselves,
serve as sources of radiated noise.
U.S.A.
Canada
Europe
NEMKO
Part No.
UL(NRTL)
CSA
UL1283
[250V]
CSA C22.2 No.8
[250V]
EN60939
[430V]
P08209031
Rated voltage
ZRCF4230-02B
2500010138
LR76849C
APPLICATIONS
• For the CISPR frequency band, this product provides superior
attenuation for both differential mode and common mode noise
components.
Computers, general purpose inverters, UPE(uninterruptible power
equipment), computer control devices, NC control devices, etc.
Highly recommended for large equipment destined for CE coun-
tries, where compliance with EMC radiation standards is required
as part of CE marking certification.
• Single-direction block terminal design simplifies wiring require-
ments, thereby improving workflow.
• It is a product conforming to RoHS directive.
SHAPES AND DIMENSIONS
220
203
239
M4
4-ø5.5
Dimensions in mm
• Case:metal, terminal cover:polycarbonate,
terminal block:cross recessed head screws, cover surface:long hole 4× 20mm punching
ELECTRICALCHARACTERISTICS
Part No.
ZRCF4230-02B
[Between terminal]
[Between terminal and ground]
[Between terminal and N-terminal]
430
250
250
Rated voltage
Eac(V)
Rated current(A)
30
Test voltage Eac(V)[Between terminal and case]
Insulation resistance(MΩ)[DC. 500V, 1min/between terminal and case]
Leakage current(mA)[415V • 60Hz]
DC resistance(mΩ)
Operating temperature range(°C)[Including self-temperature rise]
2000
300min.
3.0max.
50max.
–25 to +55
55
With derating over(°C)
Temperature rise(°C)
40max.
0.2 to 8
0.2 to 8
1.7
Differential mode at 40dB
Common mode at 40dB
Attenuation frequency range
(MHz)[+5 to +35°C]
Weight(kg)
• Conformity to RoHS Directive: This means that, in conformity with EU Directive 2002/95/EC, lead, cadmium, mercury, hexavalent chromium, and specific
bromine-based flame retardants, PBB and PBDE, have not been used, except for exempted applications.
• All specifications are subject to change without notice.