Protection Relays
Voltage Monitoring Relays
WVM SERIES
Description
The WVM Series provides protection against premature
equipment (motor) failure caused by voltage faults on the
3-phase line. The WVM’s microcontroller design provides reliable
protection even if regenerated voltages are present. It combines
dependable fault sensing with a 10 fault memory and a 6 LED
status display. Part instrument, part control, the WVM protects
your equipment when you’re not there and displays what
happened when you return. The WVM is fully adjustable and
includes time delays to prevent nuisance tripping and improve
system operation. Time delays include a 0.25 to 30s adjustable
trip delay, an adjustable 0.25 to 64m (in 3 ranges) restart delay,
plus a unique 3 to 15s true random start delay. The random start
delay prevents voltage sags caused by simultaneous restarting
of numerous motor loads after a power outage.
Wiring Diagram
Features & Benefits
FEATURES
BENEFITS
Proprietary
microcontroller
based circuitry
Constant monitoring to protect against phase loss,
phase reversal, over voltage, under voltage,
unbalance, and short cycling
F = Fuses
Stores the 10 most recent faults, which provides
diagnostics for troubleshooting
NO = Normally Open
NC = Normally Closed
RS = Optional Remote
Reset Switch
Fault memory
LED indication
Provides visual indictation of existing relay/fault
status or faults stored in memory.
Switch selectable
automatic restart,
Allows user adjustment to handle unique
application requirements
Relay contacts are isolated.
delayed automatic
restart, and manual reset
CAUTION: 2 amp max fast acting fuses must be
installed externally in series with each input. (3)
Prevents voltage sags caused by simultaneous
restarting of multiple motor loads after a
power outage
Random start delay
Operation
The output relay is energized when all conditions are acceptable
and the WVM is reset. A restart and/or random start delay may
occur before the output relay is energized.
Field Adjustment: Select the line voltage listed on the motor’s
name plate. This automatically sets the over and undervoltage
trip points. No further adjustment should be required to achieve
maximum equipment protection.
Ordering Information
MODEL
LINE VOLTAGE
UNBALANCE
TRIP DELAY
SWITCH SELECTABLE RESET METHOD RESTART DELAY
WVM011AL
WVM611AH
WVM611AL
WVM611RL
WVM811AH
WVM811RL
WVM911AH
WVM911AL
WVM911AL-60
WVM911AN
WVM911RH
WVM911RL
WVM911RN-60
500 to 600VAC
200 to 240VAC
200 to 240VAC
200 to 240VAC
355 to 425VAC
355 to 425VAC
400 to 480VAC
400 to 480VAC
400 to 480VAC
400 to 480VAC
400 to 480VAC
400 to 480VAC
400 to 480VAC
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
2 - 10%
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
0.25 - 30s
Auto restart upon fault trip
Auto restart upon fault trip
Auto restart upon fault trip
Auto restart upon fault correction
Auto restart upon fault trip
Auto restart upon fault correction
Auto restart upon fault trip
Auto restart upon fault trip
Auto restart upon fault trip
Auto restart upon fault trip
Auto restart upon fault correction
Auto restart upon fault correction
Auto restart upon fault correction
0.25 - 64s
0.25 - 64m
0.25 - 64s
0.25 - 64s
0.25 - 64m
0.25 - 64s
0.25 - 64m
0.25 - 64s
0.25 - 64s, no random start delay
6 - 300s
0.25 - 64m
0.25 - 64s
6 - 300s, no random start delay
If you don’t find the part you need, call us for a custom product 800-843-8848
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/wvm
Rev: 1-A-062716