350W Single Output with PFC Function
USP-350 series
Features :
Universal AC input / Full range
Built in active PFC circuit compliance to EN61000-3-2
Protections: Short circuit / Overload / Over voltage / Over temperature
Free air convection for 300W and 350W with 23.5CFM forced air
High power density 6.3w/in3
ZVS technology to reduce power dissipation
Active AC surge current limiting
U-bracket low profile:38mm
3 years warranty
SPECIFICATION
MODEL
USP-350-3.3
USP-350-5
USP-350-12
USP-350-15
USP-350-24
USP-350-48
DC VOLTAGE
RATED CURRENT
3.3V
70A
5V
12V
15V
24V
48V
70A
29.2A
23.4A
14.6A
7.3A
CURRENT RANGE (convection) 0 ~ 50A
CURRENT RANGE (23.5CFM FAN) 0 ~ 70A
RATED POWER (convection) 165W
RATED POWER (23.5CFM FAN) 231W
RIPPLE & NOISE (max.) Note.2 80mVp-p
0 ~ 50A
0 ~ 70A
250W
350W
80mVp-p
4.5 ~ 5.5V
2.0%
0 ~ 25A
0 ~ 29.2A
300W
0 ~ 20A
0 ~ 23.4A
300W
0 ~ 12.5A
0 ~ 14.6A
300W
0 ~ 6.25A
0 ~ 7.3A
300W
350.4W
100mVp-p
10.8 ~ 13.2V
2.0%
351W
350.4W
150mVp-p
21.6 ~ 26.4V
2.0%
350.4W
150mVp-p
43.2 ~ 52.8V
2.0%
OUTPUT
100mVp-p
13.5 ~ 16.5V
2.0%
VOLTAGE ADJ. RANGE
2.97 ~ 3.6V
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
2.0%
2.0%
1.0%
1.0%
1.0%
1.0%
2000ms, 100ms/230VAC
4000ms, 100ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
12ms/230VAC
Note.5 90 ~ 264VAC
47 ~ 63Hz
16ms/230VAC
127 ~ 370VDC
16ms/115VAC at full load
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
0.94/230VAC
78%
0.95/230VAC
84%
0.98/115VAC at full load
88%
88%
88%
89%
INPUT
4A/115VAC
2A/230VAC
44A/230VAC
22A/115VAC
<2mA / 240VAC
105 ~ 120% rated output power
105 ~ 130% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
3.7 ~ 4.6V 5.7 ~ 7V 13.5 ~ 16.3V 17 ~ 21V 26.7 ~ 32.4V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
80 (TSW1) detect on heatsink of power transistor 80 (TSW2 ) detect on heatsink of power diode
53 ~ 64.8V
OVER VOLTAGE
OVER TEMPERATURE
PROTECTION
5
5
Protection type : Shut down o/p voltage with auto-recovery
-10 ~ +65 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
0.03%/ (0 ~ 45
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
SAFETY &
EMC
(Note 4)
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, light industry level, criteria A
106.3K hrs min. MIL-HDBK-217F (25
235.2*101.5*38mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
1.1Kg; 16pcs/18Kg/0.72CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:USP-350-SPEC 2008-05-06