Time Delay Relays
Dedicated - Interval
TSD7 SERIES
Interval/Delay-on-BreakTimer
Description
TheTSD7 Series utilizes only two terminals connected in series
with the load. Interval timing mode period is achieved by using a
small portion of the AC sine wave allowing sufficient voltage for
circuit operation. It can be used as an interval timer to control or
pulse shape the operation of contactors, solenoids, relays, and
lamp loads. TheTSD7 Series can be wired to delay on the break
of a switch for energy saving fan delays.
Operation (Interval)
Upon application of input voltage, the output energizes and the
time delay begins. The output remains energized throughout the
time delay. At the end of the time delay, the output de-energizes
and remains de-energized until power is removed.
Reset: Removing input voltage resets the time delay and
the output.
Wiring Diagram
Operation (Delay-on-Break)
Upon closure of SW1, the load is energized and the timer is
reset (zero volts across its input terminals). Opening SW1 re-
applies input voltage to the timer, the load remains energized
and the time delay begins. At the end of the time delay, the
output de-energizes. If SW1 is open when power is applied, the
load will energize for the time delay then de-energize.
L1
N/L2
Interval
Reset: Reclosing SW1 resets the timer.
Features & Benefits
FEATURES
BENEFITS
Repeat Accuracy + / - 0.5%,
+ / -1% time delay accuracy
Microcontroller based
Delay-on- Break
Extended
temperature range
Rated to 75°C operating temperature to withstand
high heat applications
Compact, low
cost design
V = Voltage
L = Load
S1 = Initiate Switch
RT is used when external
adjustment is ordered.
Allows flexiblility for OEM applications
1A steady solid-state
output, 10A inrush
Provides 100 million operations in typical conditions.
No moving parts to arc and wear out over time and
encapsulated to protect against shock, vibration,
and humidity
Totally solid state
and encapsulated
Two terminal series
load connections
Provides quick and easy installation for new or
existing systems
Ordering Information
MODEL
INPUT VOLTAGE ADJUSTMENT
TIME DELAY
2s
MODEL
INPUT VOLTAGE
ADJUSTMENT
Fixed
TIME DELAY
120s
TSD7412S
TSD7414M
TSD7421
TSD7423
TSD7424
120VAC
120VAC
120VAC
120VAC
120VAC
Fixed
TSD761120S
TSD761180S
TSD7611S
TSD7621
230VAC
230VAC
230VAC
230VAC
Fixed
4m
Fixed
180s
External
External
External
1 - 100s
0.1 - 10m
1 - 100m
Fixed
1s
External
1 - 100s
If you don’t find the part you need, call us for a custom product 800-843-8848
© 2016 Littelfuse Protection Relays & Controls
www.littelfuse.com/tsd7
Rev: 1-A-061016