Ordering information
Three phase input type(1-stage filter)
TAC -50 -223 -O
TAC series(50,60,80,100,150A)
1
2
3
4
1Model Name
2Rated Current
3Line to ground capacitor code:See table 1.1.
R
table1.1 Line to ground capacitor code
Line to ground
Leakage Current
(Input 250/500V 60Hz)
Code
capacitor
(nominal value)
10,000pF
103
223
333
1.0mA/2.0mA max
2.5mA/5.0mA max
3.5mA/7.0mA max
22,000pF
33,000pF
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
*
4Option
U:Improve differential mode attenuation
(Rated voltage 250V)
Features of TAC series
High-attenuation type of common mode noise from 150kHz to 1MHz (1-stage filter)
-Three phase rated voltage 500 VAC (voltage range:528V max)
-Selectable leakage current value
Specifications
No.
1
Items
TAC-50-223
AC Three Phase 500 (voltage range:528 max) 50/60Hz *1
50 60 80 100
TAC-60-223
TAC-80-223
TAC-100-223
TAC-150-223
Rated Voltage[V]
2
Rated Current[A]
150
3
Test Voltage (Terminal-Mounting Plate)
2,500 VAC (Cutoff Current = 100mA), 1minute at room temperature and humidity
4
Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MWmin at room temperature and humidity
5
6
Leakage current 250/500V 60Hz
DC registance
2.5mA/5.0mA max
7mWmax
5mWmax
5mWmax
4mWmax
3mWmax
7
8
9
Safety agency approval temperatures
Operating temperature
Operating humidity
-25 to +85C(Refer to Derating Curve)
-40 to +85C(Refer to Derating Curve)
20 to 95%RH (Non condensing)
10
11
12
13
Storage temperature/humidity
Vibration
Impact
-40 to +85C/20 to 95%RH (Non condensing)
2
10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis
2
196.1m/s (20G), 11ms Once each X, Y and Z axis
Safety agency approvals
UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
90X54X179 mm (WXHXD)
[3.54X2.13X7.05 inches]
1.4kg max
140X85X267 mm (WXHXD)
[5.51X3.35X10.51 inches]
3.8kg max
170X92X285 mm (WXHXD)
[6.69X3.62X11.22 inches]
4.8kg max
14
Case size (without projection)
15
Weight
*1 Only “TAC-OOO-OOO-U”, Three Phase 250 (275 max)
Circuit Diagram
Derating Curve
(1) TAC-OOO-OOO
Case
LINE
LOAD
100
80
60
40
20
0
1
2
4
5
6
3
CY CY CY
CY CY CY
CY : Line to ground capacitor
: Mounting Plate
-40
-30 -20
40
50
60
70
80
90
(2) TAC-OOO-OOO-U (Option : U)
Ambient Temperature [C]
Case
LINE
LOAD
*Keep free ventilation holes for cooling.
1
2
4
5
3
6
CY CY CY
CY CY CY
CY : Line to ground capacitor
: Mounting Plate
NF-62