Current and Voltage Controls
3-Phase Cos ϕ Control
Type SY 115
• Load guard for asynchronous motors
and other symmetrical loads
• Measures on phase difference (cos ϕ) between motor
current and voltage
• Measuring range: Cos ϕ = 0-0.9 with 1-phase current
metering transformer, type MI...
• Knob-adjustable cos ϕ level
• Delay on operate at power ON
• Output: 10 A SPDT relay
• Plug-in type module
• S-housing
• LED-indication for power supply and output ON
• AC power supply
Product Description
3-phase load guard monitor- a motor from overload in ap- Housing
ing plug-in relay. Measures plications where stops can Function
the phase difference (cos ϕ) be- damage the whole mechani- Output
tween motor current and volt- cal system.
age. Often used for protecting
Ordering Key
SY 115 220
Type
Power supply
Type Selection
Plug
Output
Supply: 220 VAC
SY 115 220
Supply: 380 VAC
SY 115 380
Supply: 415 VAC
SY 115 415
Circular
plug
SPDT
Input Specifications
Output Specifications
Input
Pins 5, 6 & 7
Pins 8 & 11
Output
SPDT relay
250 VAC (rms)
(cont./elect.)
Phase L1, L2, L3
Rated insulation voltage
0.4-4 Vp from current trans-
former, type MI100/MI 500
black wire connected to pin 8
Contact ratings (AgCdO)
Resistive loads
µ (micro gap)
AC 1
DC 1
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
or 10 A/25 VDC (250 W)
2.5 A/230 VAC
Small inductive loads AC 15
DC 13
Supply Specifications
5 A/24 VDC
≥ 30 x 106 operations
≥ 2.5 x 105 operations
Power supply AC types
Rated operational voltage
Through pins 5, 6 & 7 220
Overvoltage cat. III (IEC 60664)
(IEC 60038)
3 x 220 VAC ± 10%,
45 to 65 Hz
3 x 380 VAC ± 10%,
45 to 65 Hz
3 x 415 VAC ± 10%,
45 to 65 Hz
≤ 40 ms
Mechanical life
Electrical life
AC 1
(at max. load)
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
≤ 7200 operations/h
380
415
≥ 2 kVAC (rms) (cont./elect.)
Voltage interruption
Dielectric voltage
None (supply/elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (line/neutral)
(line/line) direct connection
to electronics
Rated operational power
2.5 VA
Specifications are subject to change without notice (26.10.99)