SW20XX-EX Isolating Switching Barrier
FEATURES
PRODUCT PROGRAM
Input(Power)
Voltage(VDC)
● Fitted devices: 1. NAMUR Sensors;
2. Mechanical Joints.
Output(Hazardous end)
Output
(Safe end)
Channel
numbers
Part number
Voltage
Typ
Short Cricuit
Current
● Phase-angel and inverse control setting;
● Open circuit detection setting
Typ
Range
SW2001-EX
SW2002-EX
Relay output
Relay output
1
2
● Respective Isolation(2,500VDC between
Input/Output/Power source);
24
18-36
8 VDC
< 8 mA
● Operation Temperature:-20℃-+60℃
● Reliable Performance (MTBF>1,000,000 Hours).
ELECTRICAL CHARACTERISTICS
Operation voltage
18-36VDC
Common
parameter
APPLICATIONS
Power consumption
About 2.0W (with relay output OFF)
LED light (green) ON when operating
This Isolation Switching Barrier can detect
switch or approach switch’s status in locations
where hazardous exists; isolate, transmit and
output it to safe area. Input and output can be set
to inverse control. Approach switch open circuit
detection function. Isolation between Input/
Output/Power source.
Power indicating
Input Signal
Switch status of NUMAR sensor,
mechanical joint etc
Output Voltage
Hazardous
8V(Open status)
Area
Short circuit current
<8mA
Input switching frequency <10Hz
threshold
Typ:1.55mA (hysteresis:0.2mA)
Relay output(1” ON” joint)
<20ms
MODEL SELECTION
Output signal
Response time
Safe Area
SWXXXX-EX
driving capability
250VAC / 3A or 30VDC / 3A
Resistive load
Explosio n protection certification mark
Channe l number
Additional function
Signal o utput mode ( safe area)
Load type
Signal o utput mode ( hazardous a rea)
Detectin g signal type
TRANSMISSION CHARACTERISTICS
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) ON.
Under phase-angel control
(K1 “OFF”)
MORNSUN Guangzhou Science & Technology co., Ltd.
Address: 2/F, Bldg 6, Huangzhou Industrial Park,
Chebei Rd, Tianhe, Guangzhou, China 510660
Tel: 86-20-38601850 39601530 38601679
Fax: 86-20-38601272
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) OFF.
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) OFF.
http://www.mornsun-power.com
Under inverse control
(K1”ON”)
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) ON.
Open detection function
Function when K3 is OFF
Input loop current < 0.05mA, open circuit alarm, channel
red indicator light ON.
When connected with NAMUR
sensor
When connected with common To achieve open circuit detection function, a 10KΩ resistor
contact joint switch
must be connected to the switch in parallel.
ISOLATION CHARACTERISTICS
Isolation between each part (Signal input end/Signal output end/Power
source end)
Electrical isolation
Isolation strength
Surge Resist
EMC
2.5KVDC (test for 1minute, humidity < 70%)
5KV 1.2/50us (Based on IEC255-4)
EN61326
MORNSUN reserves the copyright
Specifications subject to change without notice.
SW20XX-EX
A/0-2008