Features
®
SpectrAlert SP200 Series
• Fidelity sound quality.
• Low-profile design; fits standard
4" x 4" x 2-1/8" (101.6 x 101.6 x
53.975 mm) backbox without ex-
tension ring.
Dual-Voltage Transformer Speakers
• Four field-selectable power taps:
easy to select and easy to
change (1/4 through 2 watts).
Description
System Sensor’s SP200
Series Speakers com-
bine performance, func-
tionality, and flexibility in
a line of dual-voltage
evacuation speakers.
• Dual voltage settings: 25.0 and
70.7 volts.
• Ceiling- and wall-mount applica-
tions.
• Grilles available in white and red.
• Color-matched mounting screws.
Performance — With
its low total harmonic dis-
tortion, the SpectrAlert®
SP200 Series offers fi-
delity-quality sound out-
Listings
Listings and approvals below
apply to the basic SpectAlert®
SP200 Series Dual-Voltage
Transformer Speakers. In some
cases, certain modules may not
be listed by certain approval
agencies, or listing may be in
process. Consult factory for
latest listing status.
put.
This provides
6710pho1.jpg
greater assurance that
the SP200’s output
closely matches its
source signal. This fidel-
ity sound quality is achieved at any of the SP200’s four field-selectable power
taps: 1/4, 1/2, 1, and 2 watts.
Functionality — Installation ease and functionality are achieved through
the SP200’s compact design, which allows flush-mounting to a 4" x 4" x 2-1/8"
(101.6 x 101.6 x 53.975 mm) backbox without an extension ring.
• UL Listed: file S4048.
• CSFM approved:
file 7320-1209:186.
Flexibility — The SP200 is designed for a variety of application require-
ments. Offered with round and square grilles, the SP200 can be mounted to
either the wall or the ceiling. White and red grilles are available to meet
specific aesthetic requirements.
• MEA approved: file 353-98-E.
Engineer’s Specifications
Speaker shall be a System Sensor model ______ dual-voltage transformer
speaker capable of operating at 25.0 or 70.7 nominal VRMS. Speaker shall
be Listed to Underwriters Laboratories Standard 1480 for fire protective
signaling systems. Speaker shall have a frequency range of 400 to 4,000
Hz and shall have an operating temperature between 32°F and 120°F
(0°C and 49°C). Speaker shall have power taps which are selected by
shunts.
SpectrAlert® is a registered trademark and Sync•Circuit™ is a trademark
of System Sensor.
SpectrAlert® SP200 Series CS-2454 10/21/04
Page 1 of 2