S/MOT/SMCW6151/A/23/07/99
1W240030
®
Solid Sta t e Rela ys
F or Motor Con tr ol
celduc
P a ge 1/16 GB
r
e
l
a
i
s
EXTERNALLY BYP ASSED THREE P HASE
INDUCTION MOTOR SOLID-STATE REDUCED
VOLTAGE STARTER (SOF TSTARTER) WITH
SOF TSTOP F EATURE
SMCW6151
celduc relais SMCV can be employed everywhere using a costly and relatively big variable
speed controller is not required (pumps, fans, compressors, conveyors, …).
Its six th yr ist or structure working like a full wave phase angle controller (both positive and
negative cycles are controlled), allows to reduce efficiently the induction motor starting current as well
as the motor starting torque. This m ot or sta r t in g cu r r en t r ed u ction allows to optimize the mains
grid as well as its protections and a void h a vin g volt a ge flu ct u a tion s leading to ambient light
variations also called "flicker".
Exter n a lly
Byp a ssed 3 P h a se
In d u ct ion Motor
Softsta r ter
Built to help the user to get his assembly in compliance with the European directives and
standards, this product easy fits in the existing application without any modification of the wiring
field configuration. Thus, the SMCV can easily replace an electromechanical star-delta starter
without changing the motor coupling! In a project including a three phase induction motor it can be
implemented like a usual three phase electromechanical contactor. Furthermore, its ability to be
installed inside the delta wiring allows this device to drive 1.73 t im es m or e cu r r en t than a standard
on line softstarter,
200 - 480VAC
->15k W (Y)
->26k W (D)
The SMCV also have d ia gn ost ic a n d self-t est fu n ction s to inform people involved in the
machine maintenance and t o r ed u ce t h e cost a n d t h e d ela y to r est a r t t h e p r od u ction .
MAIN CHAR ACTE RISTICS
Ma x. Mot or P ow er @40°C
Wit h E xt er n a l Byp a ss
IAC53b @40°C
Wit h E xt . Byp a ss
P h a se
t o
P h a se
Volt a ge
Op er a t in g
In /Ou t /Ca se
Tem p er a -
Ma in s
F r equ en cy
St a t u s
Ou tp u ts
In p u t
10 t o
St a r (Y)
Delta (D)
Isola t ion
t u r e
Ma x. EN60947-4-2
400VAC 230VAC 400VAC 230VAC
200 t o
480VAC
24V / 1A
24VDC AC/DC
-40 t o
+100°C
15k W
8.6k W
26k W
15k W
30A
22.5A
40 t o 65Hz
4k V
BENEFIT F OR MOTOR STAR TING
DIR E CT ON LINE (DOL) STARTING
TYP ICAL WIRINGS
DELTA (D)
STAR (Y)
Mech a n ica l p a r t st r ess:
- noise
- Maintenance costs
High in r u sh cu r r en t :
- Motor and mains
protections oversized
- Risk of flicker
SOF TSTAR TING WITH SMCV
Softst a r t in g:
- Noise reduction
- Maintenance cost
reduction
No m or e h igh in r u sh
cu r r en t :
- Motor and mains
protections optimization
- No more harmonic or
flicker problems
®
Proud to serve you
celduc
Characteristics may change without notice
r e l a i s