5秒后页面跳转
SMB500 PDF预览

SMB500

更新时间: 2024-11-16 06:12:19
品牌 Logo 应用领域
GAMEWELL-FCI 继电器
页数 文件大小 规格书
4页 512K
描述
Addressable Control and Relay Modules

SMB500 数据手册

 浏览型号SMB500的Datasheet PDF文件第2页浏览型号SMB500的Datasheet PDF文件第3页浏览型号SMB500的Datasheet PDF文件第4页 
Features  
• Built-in type identification  
automatically identifies these  
devices to the control panel.  
SCE-SS and RCE-SS  
Addressable Control and Relay Modules  
• Internal circuitry and relay  
powered directly by two-wire  
SLC loop. The SCE-SS module  
requires power (for horns,  
strobes, etc.), audio (for speak-  
ers), or a telephone riser (for  
handsets). Internal relay feature  
available on SmartScan™  
systems only.  
Description  
SCE-SS Control Module — The SCE-SS  
Addressable SmartScan™ Control Module  
provides Gamewell intelligent control pan-  
els a circuit for Notification Appliances  
(horns, strobes, speakers, etc.) or to moni-  
• Use with IF602, 610, 632, 654  
and 658.  
tor a telephone circuit.Addressability allows  
TENS  
• Integral LED “blinks” green each  
time a communication is  
received from the control panel  
and turns on in steady red when  
activated.  
the SCE-SS to be activated, either manu-  
ally or through panel programming, on a  
select (zone or area of coverage) basis.  
ONES  
RCE-SS Relay Module — The RCE-SS  
Addressable Relay Module provides the  
system with a dry-contact output for acti-  
vating a variety of auxiliary devices, such  
as fans, dampers, control equipment, etc.  
Addressability allows the dry contact to  
be activated, either manually or through  
panel programming, on a select basis.  
• LED blink may be deselected  
globally (affects all devices).  
• High noise immunity (EMF/RFI).  
SCE-SS Module  
(See wiring diagram Fig. 5 for RCE-SS)  
• The SCE-SS may be used to  
switch 24-volt NAC power, audio  
(up to 70.7 VRMS) or telephone.  
Applications  
• Wide viewing angle of LED.  
The SCE-SS is used to switch 24 VDC audible/visual power, high-level audio (speak-  
ers), or control telephone devices. The RCE-SS may be programmed to operate dry  
contacts for door holders, Air Handling Unit shutdown, etc., and to reset four-wire  
smoke detector power.  
• SEMS screws with clamping  
plates for wiring ease.  
• Direct-dial entry of address 01–  
99 for SmartScan™.  
Construction  
• Speaker, audible/visual, and  
telephone applications may be  
wired for Class B or A (Style Y or  
Z).  
• The face plate is made of off-white Noryl®.  
• Controls include two rotary switches for direct-dial entry of address (01-99).  
• The SCE-SS is configured for a single Class B (Style Y) or Class A (Style Z)  
Notification Appliance Circuit.  
• The RCE-SS provides two Form-C dry contacts that switch together.  
Listings  
Operation  
Listings and approvals below  
apply to the SCE-SS & RCE-SS  
Series Addressable Control and  
Relay Modules. In some cases,  
certain modules may not be  
listed by certain approval  
Each SCE-SS or RCE-SS uses one of 99 possible module addresses on a SLC loop.  
It responds to regular polls from the control panel and reports its type and status,  
including the open/normal/short status of its Notification Appliance Circuit (NAC). The  
LED blinks with each poll received. On command, it activates its internal relay. The  
SCE-SS supervises Class B (Style Y) or Class A (Style Z) notification or control cir-  
cuits.  
agencies, or listing may be in  
process. Consult factory for  
latest listing status.  
Upon code command from the panel, the SCE-SS will disconnect the supervision and  
connect the external power supply in the proper polarity across the load device. The  
disconnection of the supervision provides a positive indication to the panel that the  
control relay actually turned ON. The external power supply is always relay isolated  
from the communication loop so that a trouble condition on the external power supply  
will never interfere with the rest of the system.  
• UL Listed: file S521.  
• CSFM approved:  
file 7300-1288:171.  
Rotary switches set a unique address for each module. The address may be set be-  
fore or after mounting. The built-in TYPE CODE (not settable) will identify the module  
to the control panel, so as to differentiate between a module and a sensor address.  
SmartScan™ is a trademark of Gamewell.  
SCE-SS and RCE-SS CS-2466 09/01/06  
Page 1 of 4  

与SMB500相关器件

型号 品牌 获取价格 描述 数据表
SMB-501M SUNMATE

获取价格

Protection Devices Glass gas discharge tube
SMB5072A1-NT30G-50 AMPHENOL

获取价格

RF Connector Adapter, SMB-SMB, Male-Female
SMB51 MIC

获取价格

SURFACE MOUNT TRANSIENT VOLTAGE SUPPRESSOR
SMB51 LITEON

获取价格

SURFACE MOUNT UNIDIRECTIONAL AND BIDIRECTIONAL TRANSIENT VOLTAGE SUPPRESSORS
SMB51A MIC

获取价格

SURFACE MOUNT TRANSIENT VOLTAGE SUPPRESSOR
SMB51A LITEON

获取价格

SURFACE MOUNT UNIDIRECTIONAL AND BIDIRECTIONAL TRANSIENT VOLTAGE SUPPRESSORS
SMB51A / CA-AH SWST

获取价格

瞬态电压抑制管
SMB51C LITEON

获取价格

SURFACE MOUNT UNIDIRECTIONAL AND BIDIRECTIONAL TRANSIENT VOLTAGE SUPPRESSORS
SMB51CA LITEON

获取价格

SURFACE MOUNT UNIDIRECTIONAL AND BIDIRECTIONAL TRANSIENT VOLTAGE SUPPRESSORS
SMB51-FREQ-OUT23 CONNOR-WINFIELD

获取价格

CMOS/TTL Output Clock Oscillator, 3.84MHz Min, 125MHz Max