1
RY2
Plug-in power relays
• General purpose relays
• Plug-in version - rail mount TH35, EN 50022
Contacts
2C/O
AgCdO
Contacts
Contact number & arrangement
Contact material
Voltage
250 V / 250 V
10 V
Max. switching voltage AC/DC
Min. switching voltage AC/DC
Current
12 A / 250 V AC
12 A / 30 V DC
20 A
Rated load
AC1
DC1
Max. switching current
Min. inrush current
Rated current
10 mA
12 A
3 000 VA
0,5 W
£ 100 mW
Max. breaking capacity
Min. breaking capacity
Resistance
AC1
at 100 mA, 24 V
Max. operating frequency
• at rated load
• no load
1 200 cycles/hour
18 000 cycles/hour
Coil
on
Coil
Voltage
Rated voltage
5...220 V DC
6...230 V AC 50 Hz, 6...240 V AC 50/60 Hz
Must release voltage
n
n
³ 0,1 U DC; ³ 0,2 U AC
Operating range of supply voltage
Rated power consumption
see Tables 1, 2, 3
0,9 W DC
1,6 VA AC 50 Hz; 1,9 VA AC 50/60 Hz
Insulation
Insulation category
B250
Voltage
250 V AC
Insulation rated voltage
Dielectric strength:
• coil-contact
2 500 V AC
1 000 V AC
2 500 V AC
• contact-contact
• pole-pole
Contact-coil distance
• clearance
• creepage
³ 2,6 mm
³ 4 mm
General data
V
15 ms
10 ms
General data
Operating time (typical value)
Release time (typical value)
Electrical life
³ 105
see Fig. 2
³ 107
27,5 x 21,1
35 g
at 12 A 250 V AC
• resistive
• cos j
Mechanical life (cycles)
Dimensions (L x W x H)
Weight
x 34,5 mm
Ambient temperature
• storing
• operating
°C
°C
-40...+70
-40...+55
Cover protection category
Shock resistance
Vibration resistance
IP 40
10 g
5 g
for 15...150 Hz