MODEL: R3-NP1  
Remote I/O R3 Series  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
PROFIBUS-DP INTERFACE MODULE  
/C02: Polyurethane coating  
27.5 [1.08]  
/C03: Rubber coating  
CAUTION  
■ Mounting on 2-slot base  
130  
[5.12]  
Use a dedicated base (R3-BS02P) for R3-NP1.  
115.1  
[4.53]  
GENERAL SPECIFICATIONS  
Connection  
mm [inch]  
PROFIBUS: 9-pin D-sub connector, female  
Internal bus: Via the Installation Base (model: R3-BSx)  
Internal power: Via the Installation Base (model: R3-BSx)  
Power input, RUN contact output: M3 separable screw  
terminal (torque 0.5 N·m)  
MODEL: R3-NP1-[1][2]  
ORDERING INFORMATION  
• Code number: R3-NP1-[1][2]  
Specify a code from below for each of [1] and [2].  
(e.g. R3-NP1-R/CE/Q)  
Screw terminal: Nickel-plated steel  
Isolation: PROFIBUS to internal bus or internal power to  
power supply to RUN contact output to FG  
Input error data setting: Input value setting at input module  
error with side DIP SW  
• Specify the specification for option code /Q  
(e.g. /C01)  
Dual communication setting: Set with the side DIP switch  
RUN indicator: Bi-color (green/Amber) LED  
(Function selected with DIP SW)  
[1] POWER INPUT  
N: No power supply  
ERR indicator: Bi-color (green/red) LED  
(Function selected with DIP SW)  
AC Power  
RUN CONTACT OUTPUT  
K3: 100 – 120 V AC  
RUN contact: Turns ON while the green RUN LED is ON.  
(PROFIBUS in normal communication)  
Rated load: 250 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
(Operational voltage range 85 - 132 V, 47 - 66 Hz) *  
(CE not available)  
L3: 200 – 240 V AC  
(Operational voltage range 170 - 264 V, 47 - 66 Hz) *  
(CE not available)  
(Less than 50 V AC to conform with EU Directive)  
Maximum switching voltage: 250 V AC or 30 V DC  
Maximum switching power: 250 VA or 150 W  
Minimum load: 1 V DC @ 1 mA  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *  
* Not selectable for use with independent power modules or  
network modules with the internal power input options.  
Mechanical life: 2 × 10 cycles (300 cycles/min.)  
7
When driving an inductive load, external contact protection  
and noise quenching recommended.  
[2] OPTIONS (multiple selections)  
Standards & Approvals  
blank: Without CE  
PROFIBUS COMMUNICATION  
Interface: PROFIBUS-DP, slave (RS-485 isolation)  
Max. baud rate: 12 Mbps  
/CE: CE marking  
Protocol: DPV1  
Other Options  
Station No. setting: Rotary switch; 00 - 7D  
(Address is 7D even setting greater value)  
GSD file: Msys093F.GSD  
blank: none  
/Q: Option other than the above (specify the specification)  
GSD files are downloadable at M-System’s web site or at  
PROFIBUS International site (www.profibus.com).  
Input data: Max. 240 bytes  
Output data: Max. 240 bytes  
R3-NP1 SPECIFICATIONS  
ES-8418 Rev.15 Page 1/5  
https://www.m-system.co.jp/  

与R3-NP1L3相关器件

型号 品牌 描述 获取价格 数据表
R3-NP1L3/CE MSYSTEM Remote I/O R3 Series PROFIBUS-DP INTERFACE MODULE

获取价格

R3-NP1L3/Q MSYSTEM Remote I/O R3 Series PROFIBUS-DP INTERFACE MODULE

获取价格

R3-NP1R MSYSTEM Remote I/O R3 Series PROFIBUS-DP INTERFACE MODULE

获取价格

R3-NP1R/CE MSYSTEM Remote I/O R3 Series PROFIBUS-DP INTERFACE MODULE

获取价格

R3-NP1R/Q MSYSTEM Remote I/O R3 Series PROFIBUS-DP INTERFACE MODULE

获取价格

R3-PA16 MSYSTEM Remote I/O R3 Series TOTALIZED PULSE INPUT MODULE

获取价格