MODEL: R3-NF3
0.2 to 2.5 mm , stripped length 7 mm)
2
Remote I/O R3 Series
Internal bus: Via the Installation Base
(model: R3-BSx)
T-Link INTERFACE MODULE
(Fuji Electric T-Link capsule equivalent)
Internal power: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output: M3 separable screw
terminal (torque 0.5 N·m)
27.5
(1.08)
Screw terminal: Nickel-plated steel
Isolation: T-Link to internal bus or internal power to power
input to RUN contact output to FG
Input error data setting: Input value setting at input module
error with side DIP SW
130
(5.12)
Dual communication setting: Set with the side DIP switch
Data allocation setting: Set with the side DIP switch
I/O Points setting: Set with the front DIP switch
Data setting: Set with the front DIP switch
I/O Module Status setting: Set with the front DIP switch
I/O Type setting: Set with the front DIP switch
Analog Data Type setting: Set with the front DIP switch
RUN indicator: Bi-color (green/red) LED; Green ON in normal
communication; Red blinks when receiving data (Function
selected with DIP SW)
109
(4.29)
mm (inch)
MODEL: R3–NF3–[1][2]
ORDERING INFORMATION
• Code number: R3-NF3-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NF3-M2/Q)
ERR indicator: Bi-color (green/red) LED; Green ON in
communication errors or minor failure, blinks at errors in the
internal circuits; Red blinks when transmitting data
(Function selected with DIP SW)
• Specify the specification for option code /Q
(e.g. /C01)
■ RUN CONTACT OUTPUT
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
[1] POWER INPUT
N: No power supply
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)*
Mechanical life: 2 × 10 cycles (rate 300 cycles/min.) When
7
DC Power
driving an inductive load, external contact protection and
noise quenching recommended.
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or
network modules with the internal power input options.
T-Link SPECIFICATIONS
Node address: Rotary switch; 00 – 99
Configuration: Multi-drop
[2] OPTIONS
blank: none
Communication: Half-duplex
Baud rate: 500 kbps
/Q: With options (specify the specification)
Transmission media/distance:
KPEV-SB, 0.75 mm
2
× 1 pair, 700 m
× 1 pair, 1000 m
T-KPEV-SB, 1.25 mm
2
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
INSTALLATION
Power consumption
•AC: ≤ 22 VA
/C02: Polyurethane coating
/C03: Rubber coating
•DC: ≤ 9 W
Current consumption (no power supply): 120 mA
Output current (power supply): 230 mA continuous at 20 V
DC; 380 mA for 10 minutes
GENERAL SPECIFICATIONS
Connection
T-Link: Euro type connector terminal (applicable wire size:
R3-NF3 SPECIFICATIONS
ES-8288 Rev.2 Page 1/7
http://www.m-system.co.jp/