QM8 Series
https://emea.lambda.tdk.com/qm
https://product.tdk.com/en/power/qm
1200W - 2000W
Modular power supply
Medical
Industrial
Test
Broadcast
Renewable
Comms
Features
Benefits
•ꢀBF ready medical isolation (MOPP)
•ꢀLow speed, low audible noise fans
•ꢀUp to 18 outputs
Eases design into systems (including BF)
Enhanced patient / user experience
Eliminates need for additional supplies
Remote monitoring and control
Low cost of ownership
•ꢀPMBus™ communication option
•ꢀ7 year warranty
Input
QM8
QM8B
Output power -
Output power -
Frequency
90-264Vac
1200W
180-264Vac
1500W
2000W
47 - 63 Hz (440Hz with reduced PFC)
Input fuses
25A / 250Vac HBC Fast acting (not user accessible) in both Live and Neutral lines (single fusing optional)
<45A at 25°C and 264Vac (cold start)
Inrush current
Leakage current
Touch current
Power factor
See ‘How To Create A Product Description’ for details
<100µA (with 4 or fewer modules). For other configurations, contact sales for details.
> 0.95 (at 230Vac, 100% load)
Isolation
2 x MOPPs (3rd edition 60601)
Reinforced
Input to output / signals
4kVac, 5.7kVdc type tested to 4kVac (equivalent to 5.7kVdc), production tested to 4.3kVdc.
Input to earth
Basic
Basic
1 x MOPP, 1.5kVac
1 x MOPP, 1.5kVac
200Vdc
Output / signals to earth
Output / signals to output / signals Basic
How To Create A Product Description
The extensive range of output modules and options make it possible to achieve almost any combination of Volts and Amps. You can create
your own QM configuration online at https://config.emea.tdk-lambda.com/. This method checks your configuration and offers the optimum
solution. Alternatively, you can do this manually by using the guide below.
1.
Calculate total output power to select the appropriate converter, then select required Cooling, Connection, Leakage Current and Controls/
Signals from the following table:
QM8
F
S
D
L
T5H
blank none
E5L 5V / 250mA, Enable
QM8 1500W high line
QM8B 2000W high line
Converter
8 slots wide
E5H 5V / 2A, 5V / 250mA, Enable
E12H 12V / 1A, 5V / 250mA, Enable
T5L 5V / 250mA, Inhibit
T5H 5V / 2A, 5V / 250mA, Inhibit
T12H 12V / 1A, 5V / 250mA, Inhibit
Standby
/ Signals
F
R
C
Variable speed Forward air - standard
Reverse air (contact sales for details)
Customer air - no fan (contact sales for details)
Cooling
P5H
5V / 2A, see PMBus™ app note
see specification page for details
Input
Connection
S
Screw
Leakage Current
L
214µA
77µA
D
E
Dual AC fuses
Single AC fuse in Live line
(contact sales for details)
(max at 264Vac, 63Hz)
Input fuse
Must also add the leakage current from
modules and options
R
2.
3.
Select Output Modules using the output voltages tables and the module specifications.
Contact TDK-Lambda to validate configuration and issue a part number.
QM8_Datasheet_260431 - v11.0
1
QM8 Series