120W Single Output Power Supply or Battery Charger
PS-120 series
Features :
AC input range selected by switch
Built-in passive PFC function compliance to EN61000-3-2
With AC ON-OFF switch
3 poles AC inlet with fuse holder
Protections: Short circuit / Overload / Over voltage / Over temperature
Charger type can be selected (Optional)
Charger for lead-acid batteries
2 color LED loading indicator
Open frame models available (Without safety approval)
Low cost, High reliability
2 years warranty
TUV
Rheinland
Product Safety
geprUfre
Sicherheit
P A 120 P 13 C
S:Power Supply
A:Voltage detector
B:Current detector
:O.D.M. number
P:Open P.C.B.
C:With case
P:With PFC
N:None PFC
13:13.8V
27:27.6V
54:55.2V
SPECIFICATION
MODEL
PS-120-13P/C
PS-120-27P/C
PS-120-54P/C
DC VOLTAGE
13.8V
27.6V
54V
RATED CURRENT
CURRENT RANGE
RATED POWER
7.2A
4.3A
2.2A
0 ~ 7.2A
99.36W
0 ~ 4.3A
118.68W
200mVp-p
24 ~ 30V
1.0% 8.0%
1.0%
0 ~ 2.2A
118.8W
250mVp-p
48 ~ 60V
1.0% 7.5%
1.0%
RIPPLE & NOISE (max.) Note.2 150mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
12 ~ 15V
VOLTAGE TOLERANCE Note.3 3.0% 8.5%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
1.0%
1.0% 6.0%
1.0% 5.0%
1.0% 5.0%
1000ms, 50ms at full load
16ms at full load
VOLTAGE RANGE
88 ~ 132VAC / 176 ~ 264VAC selected by switch
47~63Hz
248 ~ 370VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
>0.65 (with PFC series)
INPUT
77%/70%
81%/76%
82%/78%
3A/115VAC
1.5A/230VAC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
COLD START 25A/115VAC
<1.5mA / 240VAC
50A/230VAC
LEAKAGE CURRENT
105 ~ 150% rated output power
OVERLOAD
Protection type : Hiccup mode, recovers automatically after fault condition is removed
15 ~ 17V 30 ~ 35V 60 ~ 66V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
RTH2 70 10 detect on RTH2 thermistor
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
Protection type : Hiccup mode, recovers automatically after fault condition is removed
-10 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
ENVIRONMENT
-20 ~ +85 , 10 ~ 95% RH
0.05%/ (0 ~ 45
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1, EN60335, EN60335-1, EN60335-2-29 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
SAFETY &
EMC
(Note 4)
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
249.5K hrs min. MIL-HDBK-217F (25
PCB Type:144*90*33mm External case type:180*96*49mm (L*W*H)
1.1Kg; 16pcs / 17.9Kg / 1.47CUFT(without PFC) 1.24Kg; 16pcs / 20.1Kg / 1.47CUFT(with PFC)
)
OTHERS
NOTE
DIMENSION
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. With PFC I/P range: 95~132VAC/190~264VAC.
6. For open P.C.B. WITH 17.8CFM min. Forced air.