5秒后页面跳转
PLR120A PDF预览

PLR120A

更新时间: 2024-09-25 14:56:35
品牌 Logo 应用领域
力特 - LITTELFUSE /
页数 文件大小 规格书
2页 367K
描述
工作原理 The output relay is energized and the LED glows when all voltages are acceptable and the phas

PLR120A 数据手册

 浏览型号PLR120A的Datasheet PDF文件第2页 
Protection Relays  
Voltage Monitoring Relays  
PLR SERIES  
Description  
The PLR Series provides a cost effective means of preventing  
3-phase motor startup during adverse voltage conditions. Proper  
A-B-C sequence must occur in order for the PLRs output  
contacts to energize. In addition, the relay will not energize  
when an undervoltage or phase loss condition is present. The  
PLR Series protects a motor against undervoltage operation.  
The adjustment knob sets the undervoltage trip point.  
8-PIN  
Operation  
The output relay is energized and the LED glows when all  
voltages are acceptable and the phase sequence is correct.  
Undervoltage must be sensed for a continuous dropout delay  
period before the relay de-energizes. Reset is automatic upon  
correction of the fault condition. The output relay will not  
energize if a fault condition is sensed as power is applied.  
Wiring Diagram  
Field Adjustment:Turn the adjustment knob fully  
counterclockwise and apply three-phase power. The LED should  
be ON. Increase adjustment until the LED goes OFF. Decrease  
adjustment until LED glows again. If nuisance tripping occurs,  
decrease the adjustment slightly.  
F = Fuses  
ØA = Phase A = L1  
ØB = Phase B = L2  
ØC = Phase C = L3  
NO = Normally Open  
NC = Normally Closed  
NOTE: When properly adjusted and operating in an average system, a voltage unbalance of 10%  
or more is required for phase loss detection. When a phase is lost while the motor is running, a  
voltage will be induced into the open phase nearly equal in magnitude to the normal phase-to-  
phase voltage. This condition is known as regeneration. When regenerated voltages are present,  
the voltage unbalance during single phasing may not exceed 10% for some motors. The PLR  
Series may not provide protection under this condition. For systems that require superior phase  
loss protection, select the PLMU Series.  
Relay contacts are isolated  
2A fast acting fuses recommended for  
safety (not required).  
Features & Benefits  
FEATURES  
BENEFITS  
Prevents 3-phase motor startup when undervoltage  
or phase loss condition is present  
Continuous monitoring  
Industry standard 8-pin  
octal plug connection  
Eliminates need for special connectors  
Quick visual indication of output status and correct  
phase sequence  
LED indication  
Ordering Information  
MODEL  
LINE VOLTAGE  
95 to 140VAC  
190 to 270VAC  
340 to 450VAC  
380 to 500VAC  
PLR120A  
PLR240A  
PLR380A  
PLR480A  
If you don’t find the part you need, call us for a custom product 800-843-8848  
© 2016 Littelfuse Protection Relays & Controls  
www.littelfuse.com/plr  
Rev: 1-A-062716  

与PLR120A相关器件

型号 品牌 获取价格 描述 数据表
PLR131 ETC

获取价格

Technical Data Sheet Photo link Light Receiver Unit
PLR132 ETC

获取价格

Photo-link Light Receiver Unit
PLR135 EVERLIGHT

获取价格

Technical Data Sheet Photo link Light Receiver Unit
PLR135/T EVERLIGHT

获取价格

Receiver, 16Mbps, Surface Mount,
PLR135/T1 EVERLIGHT

获取价格

Receiver, 16Mbps, Through Hole Mount, ROHS COMPLIANT, PACKAGE-3
PLR135/T10 EVERLIGHT

获取价格

Receiver, 16Mbps, Through Hole Mount,
PLR135/T4 EVERLIGHT

获取价格

Fiber Optic Device
PLR135/T5 EVERLIGHT

获取价格

Fiber Optic Device
PLR135/T5A EVERLIGHT

获取价格

Receiver, 16Mbps, Panel Mount
PLR135/T5P EVERLIGHT

获取价格

Receiver, 16Mbps, Panel Mount, ROHS COMPLIANT PACKAGE-3