ControlPlex Rack
®
Description – Power-D-Box
The ControlPlex® Rack is an intelligent and remotely controlla-
ble 2U power distribution system made of aluminium in a closed
housing, protected against brush contact featuring an extremely
compact design. The system has been especially designed for the
selective protection of systems with minus supply (DC -48 V or
DC -60 V) which are widely used in communication engineering. In
order to avoid voltage dips of switch-mode power supplies in the
event of overload or short circuit, protection is effected by means of
intelligent, short-circuit current limited electronic circuit protectors.
The plug-in type terminal design of the loads and the design allowing
extension in operation help to significantly reduce installation and
maintenance time.
Order number
PDB Power-D-Box® 19" (supplied standard), with ETSI
reversible flange – 19"
Technical data (T
= 25 °C, U = DC -48 V)
B
amb
Protected pole
Application:
Modular power distribution system for
short circuit current limited DC -48 V /
DC -60 V applications
Length: 84 HP (462.72 mm)
Height: 2U (88.90 mm)
Material: aluminium
ESX300-S – 300 – xx A
(with ELBus® interface)
RSI10-xxx-A
or
N
Negative pole protected
Module
CP ControlPlex-Rack
19" Power-D-Box®
xx
Number of load channels (total)
A non-redundant design
R redundant design (two supply entries, with
main and load terminals on the rear)
Main terminals
Plug-in type circuit
protectors
Plug-in type group
signalling interface
Plug-in type control
interface
R on the rear
F on the front
load terminals
RCI10-xxx-A
R
F
on the rear
on the front
Version
Rated voltage
Total current
DC -48 V…-60 V
- 2x150 A with redundant design and
line entry on the rear
A BUS
- 200 A with non-redundant design
and double line entry on the rear
PDB - N - CP 18 R- R R - A ordering example
- 100 A with non-redundant design
and line entry on the front
Preferred types
Ambient temperature
Supply terminals
-20 °C to +60 °C (without condensation)
Terminal on the rear: screw terminals,
cable cross section 16 mm²...50 mm²
Terminals on the front: screw terminals,
cable cross section 4 mm²...25 mm²
ControlPlex® Rack:
PDB –N– CP 09 A–RR-A: Supply current max. 150 A
Load current max. 30 A with 9 load channels
PDB –N– CP 09 A–FF-A: Supply current max. 100 A
Load current max. 30 A with 9 load channels
PDB –N– CP 09 A–RF-A: Supply current max. 150 A,
Load current max. 30 A with 9 load channels
PDB –N– CP 19 A–RR-A: Supply current max. 200 A
Load current max. 30 A with 19 load channels
PDB –N– CP 18 R–RR-A: Supply current max. 2 x 150 A
Load current max. 30 A with 2 x 9 load channels
Load terminals
Terminal on the rear:
plug-in type 2-pole screw terminals with
mating connector, cable cross section
0.5 mm²...6 mm²
Terminals on the front:
plug-in type 3-pole high current SUB-D
connector, cable cross section
2.5 mm²...10 mm², mating connector
(not supplied with product): see
accessories
Ground terminal
Humidity
M6 studs, always on the rear
Benefits
96 hours at 95% RH,
40 °C, to IEC 60068-2-78,
climate class 3K3 to EN60721
EN 61000-6-2 / EN 61000-6-3
3 g to IEC 60068-2-6,
approx. 2.5 kg
l
l
Designed for plug-in type electronic circuit protectors type
ESX300-S with short-circuit limitation and extended status
indication, expandable in operation.
EMC
Current per load channel 2 A...24 A
Vibration
Mass
Extremely compact installation depth 175 mm with terminals on
the front and 205 mm with rear-side terminals
With slot for signalling or control interface sub-assembly
Use of industrially manufactured power distribution modules –
protected against brush contact
7
Conformity
CE, EN60950-1
l
l
l
l
Supplied with blind covers
Other versions available on request, e.g. with back-up fuses, various
terminal connectors and cross sections, customised marking etc.
1623
www.e-t-a.de