Type PCD, AC Power Conversion Capacitors
Dual Protected, UL 810 Fail Safe, Rated 10,000 AFC
Type PCD capacitors are designed to meet the demands of AC
filter applications rich in system total harmonic distortion (THD).
This series has a patented dual protection system utilizing self
healing metallized polypropylene and a mechanical pressure
interrupter designed to operate while bus bar mounted or
bottom stud mounted to ensure a safe open circuit mode in
the event of overload or end of life.
Highlights
- Patented Dual Protection
- UL 810 Approved
- 85 ºC / 85% RH for 1000h at Vr x 1.25
- Solid Busbar Mountable
- Dry Construction
- cULus recognized File Number E71645
Specifications
Capacitance Range
20 µF to 125 µF
Capacitance Tolerance
5ꢀ ꢁtandard, 10ꢀ, ꢂ and ꢃꢀ available
Rated Voltage
240 Vac, 480 Vac, ꢂ00 Vac
–40 ºC to +70 ºC
Operating Temperature Range
Maximum Permissible Voltage (Vmax)
110ꢀ of rated rms voltage
120ꢀ of rated peak voltage (1.2 x √2x Vrms)
Maximum Permissible Current (Imax)
Terminations
1ꢃ5ꢀ of nominal rms current based on the combined effects of
harmonics, over voltages, capacitances and tolerances
Mꢂx1 Threaded tinplated brass terminals standard,
other sizes available
Maximum Rated Current (Irms)
85A ( Limited by the terminals)
Service Life Objective
ꢂ0,000 h w/94ꢀ survival rate
FIT (Failure In Time)
≤ꢃ00 x 109 component h
Maximum Short Circuit Current (available fault current)
Notes
10 kA (according to UL 810)
Additional ratings, size and terminals are available upon request.
Regulatory Information
Outline Drawing
Construction Details
Extruded aluminum with steel or
Case Material
Encapsulation
aluminum cover
Soft gel (Oil optional)
S
0.06ꢀ
Case
S
L
Diameter
(in)
Dimension
(in)
Dimension
(in)
2.50
3.00
3.50
1.250
1.375
1.375
0.487
0.630
0.630
H
+0.12ꢀ
-0.06ꢀ
L
0.020ꢀ
M12 Stud
D
0.06ꢀ
CDE Cornell Dubilier • 1605 E. Rodney French Blvd. • New Bedford, MA 02744 • Phone: (508)996-8561 • Fax: (508)996-3830