Inductive sensor
NJ6-22-N-G-5M
Technical Data
General specifications
Switching function
Normally closed (NC)
Output type
NAMUR
6 mm
flush
Rated operating distance
Installation
s
s
n
Assured operating distance
0 ... 4.86 mm
0.4
a
Reduction factor r
Reduction factor r
Reduction factor r
Output type
Al
Cu
304
0.3
0.85
2-wire
Nominal ratings
Nominal voltage
U
f
8 V
o
Switching frequency
Hysteresis
0 ... 2000 Hz
typ. %
H
Current consumption
Measuring plate not detected
Measuring plate detected
≥ 3 mA
≤ 1 mA
Functional safety related parameters
MTTF
4566 a
20 a
d
Mission Time (T
)
M
Diagnostic Coverage (DC)
Ambient conditions
0 %
0102
Ambient temperature
-25 ... 100 °C (-13 ... 212 °F)
cable PVC , 5 m
Mechanical specifications
Model Number
NJ6-22-N-G-5M
Connection type
Core cross-section
Housing material
Sensing face
2
0.75 mm
Stainless steel 1.4305 / AISI 303
PBT
IP68
Degree of protection
Cable
Features
> 10 x cable diameter
Bending radius
General information
•
•
•
Comfort series
6 mm flush
Usable up to SIL 2 acc. to IEC 61508
Use in the hazardous area
see instruction manuals
2G; 3G; 3D
Category
Compliance with standards and
directives
Standard conformity
NAMUR
EN 60947-5-6:2000
IEC 60947-5-6:1999
EN 60947-5-2:2007
IEC 60947-5-2:2007
Standards
Approvals and certificates
UL approval
cULus Listed, General Purpose
cCSAus Listed, General Purpose
CSA approval
CCC approval
CCC approval / marking not required for products rated ≤36 V
Dimensions
Pg 21
36
Electrical Connection
BN
L+
L-
BU
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0001
Germany: +49 621 776 1111
Singapore: +65 6779 9091
1
www.pepperl-fuchs.com
fa-info@us.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com