Heavy current
NH-DIN3 400V
https://www.schurter.com /PG13_14_15
Fuse NH-DIN3 400V, Transformer (gTr)
See below:
Approvals and Compliances
Description
- According to IEC 269
Weblinks
pdf data sheet, html datasheet, Detailed request for product
- According VDE 0636
- Dimensions accroding to DIN 43620
- Cut-off current characteristic on request
Unique Selling Proposition
- Characteristic gTr
- Full-range fuse-links for the protection of transformers
Technical Data
Rated Current In
Rated Voltage
Breaking Capacity
Rated Power Operating Fre-
quency fe
72- 909A
400VAC
100kA
Indicator
Basic Design
Insulator
Middle indicator
Ceramics
corrosion-resistant (rustproof)
50Hz
Metal components
Power Dissipation (Watt) operating temperature max.
The power dissipation is the so called power loss at rated current load and operation temeperature acc. VDE 0636 . It is to be measeured in Watt at
AC condition. The voltage tap is to be assured that the power dissipation of the blade contacts are included. This means the measure contact need
to be applied at the ends of the blade contacts. The standard VDE 0636 part 1 and 2 requires that following maximal permissiable power losses are
not exceeded.
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals
Compliances
The product complies with following Guide Lines
Identification
Details
Initiator
Description
REACH
SCHURTER AG
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
1