Ordering information
Single phase input type (1-Stage filter)
NAC -10 -472 -O
NAC/NAM/NAH/NAP series(4-30A)
1
2
3
4
1Series Name
2Rated Current
R
3
Line to ground capacitor code: Refer to table 1.1.
table1.1 Line to ground capacitor code
NANCANMANHAP
Line to ground
capacitor
(nominal value)
Leakage Current
Code
(Input 125/250V 60Hz)
10 A max
25 A max
50 A max
75 A max
100 A max
150 A max
000
101
221
331
471
681
102
222
332
472
● ● ●
5
A /
A /
A /
A /
A /
A /
Not Provided
100pF
220pF
330pF
470pF
● ● ● 12.5
● ● ● 25
● ● ● 37.5
● ● ● 50
● ● 75.5
●
●
●
●
●
680pF
● ● 0.13 mA / 0.25mA max 1,000pF
● ● 0.25 mA / 0.5 mA max 2,200pF
● ● 0.38 mA / 0.75mA max 3,300pF
● ● 0.5 mA / 1.0 mA max 4,700pF
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
*
4Option
D:DIN rail installation type
The terminal cover is retracted inside the unit
DIN rail installation type is option
The dimensions change when the option is set.
Refer to External view.
*
Features of NAC/NAM/NAH/NAP series
-Single Phase 250VAC (1-Stage filter)
-Quick and easy push-down terminal
Just connect the wires, push-down and tighten the screws with a screwdriver
NAC : High-attenuation type from 150kHz to 1MHz
NAH : Ultra high-attenuation type from 9kHz to 1MHz
NAM: Low leakage current type
NAP : Outside impulse high-attenuation type
Specifications
NAC-04-472
NAM-04-000
-
NAC-06-472
NAC-10-472
NAM-10-000
NAH-10-472
NAP-10-472
NAC-16-472
NAM-16-000
NAH-16-472
NAP-16-472
NAC-20-472
NAM-20-000
NAH-20-472
NAP-20-472
NAC-30-472
NAM-30-000
NAH-30-472
NAP-30-472
NAM-06-000
NAH-06-472
NAP-06-472
No.
Items
NAP-04-472
1
2
Rated Voltage[V]
Rated Current[A]
AC 1f250 / DC250
4
6
10
16
20
30
3
Test Voltage (Terminal-Mounting Plate)
2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4
Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100MWmin at room temperature and humidity
5
Leakage current
Refer to table 1.1
6
Voltage drop
1.0V max
7
8
9
10
11
12
13
14
Safety agency approval temperatures
Operating temperature
Operating humidity
Storage temperature/humidity
Vibration
-25 to +85C(Refer to Derating Curve)
-40 to +85C(Refer to Derating Curve)
20 to 95%RH (Non condensing)
-40 to +85C/20 to 95%RH (Non condensing)
2
10 to 55Hz, 19.6m/s (2G), 3min. Period, 1hour each X, Y and Z axis
2
Impact
196.1m/s (20G), 11ms Once each X, Y and Z axis
Safety agency approvals
Case size (without projection) /Weight
UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
53X41X92 mm [2.09X1.61X3.62 inches] (WXHXD) /300g max (Option : -D refer to external view)
Circuit Diagram
Derating Curve
Case
100
80
3
1
60
CY
CY
LOAD
LINE
40
20
2
4
0
-40
-30
-20
40
50 55 60
70
80
90
Ambient Temperature [C]
: Mounting Plate
CY : Line to ground capacitor
August 31, 2021