NAP
A C F I LT E R
Features
•
•
•
•
•
High-voltage pulse high attenuation type.
Single Phase 250Vac.
Selectable leakage current.
Quick and easy push down terminal.
Din rail installation type (Option).
Ordering Information
Specifications
INPUT
NAM
(1)
-10
(2)
-000
(3)
_
Voltage
250Vac/250Vdc, 1 phase
(4)
Test voltage
2.5kVac (cutoff current = 20mA), 1 minute at
(Terminal-mounting plate) room temperature and humidity.
1. Model name
2. Rated current
Isolation resistance
500Vdc, 100MW minute at room temperature and
3. Line to ground capacitor code
4. Options
D: Din rail installation type.
(Terminal-mounting plate) humidity.
OUTPUT
Current
See table.
CODE
04
CURRENT
Leakage current
Voltage drop
5mA/10mA max (125/250Vac, 60Hz)
1.0V max
4A
6A
06
10
10A
16A
20A
30A
ENVIRONMENTAL
16
Safety agency approval
Temperature
-25°C to 85°C (Refer to derating curve).
20
30
Operating temperature
Storage temperature
-40°C to 85°C (Refer to derating curve).
-40°C to 85°C
LEAKAGE
LINE TO GROUND
CAPACITOR(NOMINAL
VALUE)
CODE
CURRENT(INPUT
125/250V 60HZ)
Humidity
Vibration
20% to 95% RH (Non-condensing)
10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1 hour
each X, Y and Z axis.
000
101
221
331
471
681
102
222
332
472
5mA / 10mA max
12.5mA / 25mA max
25mA / 50mA max
Not Provided
100pF
Impact
196.1m/s2 (20G), 11ms once each X, Y and Z axis.
220pF
STANDARDS
37.5mA / 75mA max
50mA / 100mA max
75.5mA / 150mA max
0.13mA / 0.25mA max
0.25mA / 0.5mA max
0.38A / 0.75mA max
0.5mA / 1.0mA max
330pF
Safety
UL1283, CSA C 22.2 No. 8 (C-UL), DIN EN133200
VDE0565 Teil3-1, ENEC (At only AC input).
470pF
680pF
1000pF
2200pF
3300pF
4700pF
When the line to ground capacitor code is different, the attenuation
characteristic is different.
143
Your dependable power partner – www.powerbox.com.au