Description
The FCI Velociti™ Series, multi-mod six signal
output module (MMO-6SF) provides six (6), Style Y
(Class B) or three (3), Style Z (Class A) supervised
control circuits suitable for a wide range of
signaling applications. Each supervised circuit may
be used as a:
• Audio speaker circuit.
• Notification applicance circuit.
• Supervised control output.
The VelocitiTM Series use
a
communication
MMO-6SF
protocol that substantially increases the speed of
communication between the sensors and certain
FCI analog addressable fire alarm controls. These
devices operate in a grouped fashion. If one of the
devices in the group has a status change, the
panel’s microprocessor stops the group poll and
concentrates on the single device. The net effect is
response speed up to five times greater than
earlier designs.
Features
• Each MMO-6SF module provides six (6), Style Y
(Class B) or three (3), Style Z (Class A) individually
addressable, individually programmable notification
appliance or supervised output circuits.
• Removable wiring terminal blocks allow ease of
installation and servicing.
The MMO-6SF connects to the signaling line
circuits (SLC) of the FCI analog addressable series
fire alarm control panels. Each of the MMO-6SF
supervised control circuits occupies its own
address on the system’s SLC allowing each to be
fully programmable in its control-by-event
sequence of operation.
• Terminal blocks can accommodate 12 to 18 AWG
wire.
• Flexible jumper configuration feature allowing up to
three (3), output circuit addresses to be disabled.
• Accommodates multiple external power inputs.
• External power monitoring.
• Short circuit protection of external power supplies.
• Sources providing AC, DC, or audio inputs.
The address of the first supervised output circuit is
set with a pair of rotary dials. Each remaining
circuit is automatically assigned to its own
subsequent address. The MMO-6SF module
includes an address disable jumper matrix that
allows one, two, or three addresses to be turned off
to free these addresses for other purposes. An
additional jumper setting selects either Style Y or
Style Z circuit configurations. A wide range of
configurations are possible including 30 VDC,
audio input at 25 or 70.7 VRMS, 125 VAC, etc. More
than one circuit can share a power supply if the
current capacity does not exceed the power
supply’s output.
• Designed for use with FCI analog addressable series
fire alarm control panels.
• Individual LED indicators*.
• Ideal for retrofit applications.
• Two (2), mounting cabinets available for two (2),
(MBB-2 cabinet) to six (6), (MBB-6 cabinet) units.
Note: *Only the red LED is operative in panels that do not oper-
ate in Velociti™ mode.
An ISO 9001-2000 Company
Velociti™ and E3 Series™ are trademarks of Fire Control Instruments.