MODEL: MFS
Voltage
Plug-in Signal Conditioners M-UNIT
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
SPLIT-RANGE TRANSMITTER
Functions & Features
[4] OUTPUT 2
Current
• Generating two signals which control two final control
elements
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
• High-density mounting
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
Typical Applications
• Balancing two final control elements in opposite actions
used in heating-cooling or humidifying-dehumidifying
processes
[5] POWER INPUT
AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
50
(1.97)
G: 200 V AC
H: 220 V AC
J: 240 V AC
80
(3.15)
DC Power
R: 24 V DC
136
(5.35)
mm (inch)
[6] OPTIONS
blank: none
MODEL: MFS–[1]–[2][3][4]–[5][6]
/Q: With options (specify the specification)
ORDERING INFORMATION
• Code number: MFS-[1]-[2][3][4]-[5][6]
Specify a code from below for each of [1] through [6].
(e.g. MFS-V-AAA-B/Q)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
• Specify the specification for option code /Q
(e.g. /C01/S01)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
[1] OUTPUT CHARACTERISTICS
V: V-shape
GENERAL SPECIFICATIONS
Construction: Plug-in
P: Parallel
Output 2 is assigned to the reversed output in V-shape
characteristics.
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: Input or output 1 or output 2 to power
Input range: 0 – 23.2 mA DC or -1 – +12 V DC
Output range: 0 – 23.2 mA DC or -1 – +12 V DC
Output characteristics
[2] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
4: 0 – 10 V DC (Input resistance 200 kΩ min.)
I/O code combination avaliable AAA or 444 suffix codes
only.
• V-shape: two signals vary in opposite directions; used
when both final control devices have the same action (direct
-direct or reverse-reverse).
• Parallel: two signals vary in the same direction; used when
one final control device is direct and another is reverse.
Monitor jacks: Direct monitoring of output signal; accessible
at front
[3] OUTPUT 1
Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
MFS SPECIFICATIONS
ES-1379 Rev.13 Page 1/5
http://www.m-system.co.jp/