5秒后页面跳转
MDP-RB PDF预览

MDP-RB

更新时间: 2024-11-07 02:52:47
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
3页 120K
描述
Lightning Surge Protectors for Electronics Equipment M-RESTER

MDP-RB 数据手册

 浏览型号MDP-RB的Datasheet PDF文件第2页浏览型号MDP-RB的Datasheet PDF文件第3页 
MODEL: MDP-RB  
Housing material: Flame-resistant resin (black)  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
LIGHTNING SURGE PROTECTOR FOR RTD USE  
Functions & Features  
• Designed specifically for resistance temperature detector  
(RTD) circuits  
Weight: 140 g (0.31 lb), standard  
165 g (0.36 lb), with DIN rail mounting adapter  
• Protecting RTD and RTD transmitters from damage caused  
by surges on the RTD wiring  
• Absorbs surges only without affecting instrumentation  
signal  
PERFORMANCE  
Max. continuous operating voltage (Uc):  
B to C: ±6 V  
• No interruption of signal by unplugging the protector  
element  
B or C to A: ±3 V  
Line to earth: ±140 V  
Voltage protection level (Up):  
• @ 1 kV (100 A)  
2 to 3: ±32 V  
Lot.NO  
        4
2 or 3 to 1: ±16 V  
Line to earth: ±650 V  
• @ 2 kV (1 kA)  
M•STER  
MODEL  
2 to 3: ±40 V  
2 or 3 to 1: ±25 V  
Line to earth: ±800 V  
Response time: ≤ 0.1 μsec.  
Leakage current:  
MODEL: MDP–RB[1]  
ORDERING INFORMATION  
• Code number: MDP-RB[1]  
Specify a code from below for [1].  
(e.g. MDP-RB/A33/Q)  
B to C: ≤ 2 μA @ ±6 V DC  
B or C to A: ≤ 2 μA @ ±3 V DC  
Line to earth: ≤ 2 μA @ ±140 V DC  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Nominal current (I ): 100 mA  
N
Internal series resistance: 10 Ω ±0.1 %, 30 ppm/°C (17  
ppm/°F)  
Capacitance @ 1 MHz:  
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
Line to line: ≤ 1000 pF  
Line to earth: ≤ 100 pF  
Surge protection: IEC 61643-21 Categories C1, C2, D1  
/A33: With adapter (model A-33)  
Other Options  
blank: none  
STANDARDS & APPROVALS  
EU conformity:  
/Q: Option other than the above (specify the specification)  
EMC Directive  
EMI EN 61000-6-4  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
EMS EN 61000-6-2  
RoHS Directive  
/C02: Polyurethane coating  
/C03: Rubber coating  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M4 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel  
MDP-RB SPECIFICATIONS  
ES-8114 Rev.20 Page 1/3  
https://www.m-system.co.jp/  

与MDP-RB相关器件

型号 品牌 获取价格 描述 数据表
MDP-RB/A33 MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-RB/Q MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDPRO4VAF1O SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAF1S SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAF8O SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAF8S SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAP1O SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAP1S SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAP8O SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAP8S SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve