MODEL: MDP-PA  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M4 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
LIGHTNING SURGE PROTECTOR FOR  
PROFIBUS-PA  
Functions & Features  
INSTALLATION  
• Designed specifically for the network  
• No interruption of transmission signal by unplugging the  
head element module  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN  
rail mounting adapter  
Lot.NO  
        4
PERFORMANCE  
Max. continuous operating voltage (Uc):  
M•STER  
MODEL  
Line to line: 27 V  
Line to earth: ±160 V  
SHLD to earth: ±160 V  
Voltage protection level (Up):  
• @ 2 kV (1 kA)  
MODEL: MDP–PA[1]  
Line to line: ±60 V  
ORDERING INFORMATION  
• Code number: MDP-PA[1]  
Specify a code from below for [1].  
(e.g. MDP-PA/A33/Q)  
Line to earth: ±600 V  
SHLD to earth: ±600 V  
Response time:  
Line to line: ≤ 4 nsec.  
• Specify the specification for option code /Q  
(e.g. /C01)  
Line or SHLD to earth: ≤ 20 nsec.  
Leakage current:  
Line to line: ≤ 5 μA @ ±27 V  
Line to earth: ≤ 5 μA @ ±160 V  
SHLD to earth: ≤ 5 μA @ ±160 V  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
Nominal current (I ): 500 mA  
N
/A33: With adapter (model A-33)  
Other Options  
Internal series resistance: ≤ 3.3 Ω including return  
Capacitance @ 1 MHz:  
blank: none  
Line to line: ≤ 1500 pF  
/Q: Option other than the above (specify the specification)  
Line to earth: ≤ 100 pF  
SHLD to earth: ≤ 100 pF  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Surge protection: IEC 61643-21 Categories C1, C2  
/C02: Polyurethane coating  
/C03: Rubber coating  
APPLICABLE NETWORK  
PROFIBUS-PA , Foundation Fieldbus and other networks  
complied with IEC 61158-2  
Note 1: This unit is not approved for classified locations.  
Note 2: Power supply to the bus must be limited to 500 mA  
or less.  
MDP-PA SPECIFICATIONS  
ES-8207 Rev.9 Page 1/4  
http://www.m-system.co.jp/  

与MDP-PA相关器件

型号 品牌 获取价格 描述 数据表
MDP-PA/A33 MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-PA/Q MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-PM MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-PM/A33 MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-PM/Q MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-RB MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-RB/A33 MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDP-RB/Q MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MDPRO4VAF1O SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve
MDPRO4VAF1S SENSORTECHNICS

获取价格

Normally closed proportional solenoid valve