5秒后页面跳转
MAT2-4404MA PDF预览

MAT2-4404MA

更新时间: 2024-10-04 02:47:03
品牌 Logo 应用领域
爱模 - MSYSTEM /
页数 文件大小 规格书
5页 175K
描述
Lightning Surge Protectors for Electronics Equipment M-RESTER

MAT2-4404MA 数据手册

 浏览型号MAT2-4404MA的Datasheet PDF文件第2页浏览型号MAT2-4404MA的Datasheet PDF文件第3页浏览型号MAT2-4404MA的Datasheet PDF文件第4页浏览型号MAT2-4404MA的Datasheet PDF文件第5页 
MODEL: MAT2  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
[3] MAXIMUM DISCHARGE CURRENT  
M: 20kA (8/20 μsec.)  
H: 40kA (8/20 μsec.)  
LIGHTNING SURGE PROTECTOR  
[4] ALARM OUTPUT  
A: With  
FOR THREE-PHASE POWER SUPPLY  
Functions & Features  
Y: Without  
• Connected in parallel between the power and earth lines  
regardless of load current  
• Applicable to single phase 2/3-wire and threephase 3/4-  
wire system  
GENERAL SPECIFICATIONS  
Construction: Standalone; terminal access at the front  
Degree of protection: IP20 (If the solderless terminals are  
covered with insulation tubes.)  
• High discharge current capacity 20 kA or 40 kA (8/20 μs)  
• Degraded head element is automatically separated from  
the power lines by the incorporated thermal breaker, and  
the LED lamp (turns off) and the relay contact alerts the  
failure status.  
Surge protection type: Voltage limiting type one-port SPD  
Connection  
Line: M5 screw terminal (torque: 2.5 N·m)  
Alarm output: Tension clamp  
• Complies with IEC 61643-1 Class II  
Applicable wire size  
Typical Applications  
Line: See the drawing below.  
• Low-voltage distribution board  
• Combination with installation for large load current  
Alarm output: 0.13 to 1.5 mm  
2, stripped length 8 mm  
Screw terminal  
Line: Nickel-plated steel  
50 [1.97]  
Alarm output: Tin-plated copper alloy  
Housing material: Flame-resistant resin (black)  
Alarm output: SPDT relay contact trips when the thermal  
breaker operates.  
OUTPUT TERMINAL A1 – C  
98  
[3.86]  
Normal: Open  
Failure or power off: Close  
OUTPUT TERMINAL A2 – C  
60 [2.36]  
Normal: Close  
mm [inch]  
Failure or power off: Open  
Rated load:  
MODEL: MAT2–[1][2][3][4]  
250 V AC @1 A (resistive load)  
24 V DC @1 A (resistive load)  
Safety function: Thermal breaker incorporated  
Monitor LED: Green LED turns on during normal condition  
and turns off during failure condition, power off or the  
thermal breaker operating.  
ORDERING INFORMATION  
• Code number: MAT2-[1][2][3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. MAT2-2403MY)  
• Applicable Solderless Terminal Size  
diameter d  
d : M5 use  
B ≤ 13.0 mm  
[1] OPERATIONAL VOLTAGE  
240: 240 V AC  
F ≥ 7.0 mm  
(F ≥ 8.2 mm for sharing terminals)  
T ≤ 1.8 mm  
440: 440 V AC  
F
[2] POWER SYSTEM  
3: Single-phase 2/3-wire, Three-phase 3-wire  
(Select ‘240’ for ‘Operational voltage’ code.)  
4: Single-phase 2/3-wire, Three-phase 3/4-wire  
MAT2 SPECIFICATIONS  
ES-8149 Rev.12 Page 1/5  
https://www.m-system.co.jp/  

与MAT2-4404MA相关器件

型号 品牌 获取价格 描述 数据表
MAT2-4404MY MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MAT25 ETC

获取价格

Analog IC
M-AT-2L(40) HRS

获取价格

Variable Attenuator, 0MHz Min, 3000MHz Max, 0.28dB Insertion Loss-Max, ROHS COMPLIANT PACK
M-AT-2LR HRS

获取价格

Variable Attenuator, 0MHz Min, 3000MHz Max, 0.28dB Insertion Loss-Max
MAT3 ETC

获取价格

Analog IC
MAT-3 MINI

获取价格

Fixed Attenuator, 0MHz Min, 1500MHz Max, CASE A11
MAT30 ETC

获取价格

Analog IC
MAT-30+ MINI

获取价格

Fixed Attenuator, 0MHz Min, 1000MHz Max, CASE A11
MAT3-2403MA MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER
MAT3-2403MY MSYSTEM

获取价格

Lightning Surge Protectors for Electronics Equipment M-RESTER