Current Transducer HNC-40CA
IPN = 400 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
IPN
IP
Primary nominal DC or rms current
Primary current, measuring range
Measuing resistance
400
A
A
0 .. ± 800
20
RM
ISN
KN
VC
IC
W
Second nominal current
Turns ratio
100
mA
1 : 4000
± 15
Supply voltage (± 5 %)
Current consumpution
V
mA
kV
Features
20 + ISN
·
Hall effect measuring principle
Vd
R.m.s. voltage for AC isolation test, 50/60Hz, 1 min 2.0
· Panel mount type
Advantages
Accuracy-Dynamic performance data
· High accuracy
· Excellent linearity
· Low temperature drift
X
Accuracy @ TA = 25°C
< ±1 % of IPN
< ± 0.5 % of IPN
e
IO
Linearity (0 .. ± IPN)
L
·
Good response time
Electrical offset current @IP = 0, @TA = 25°C
± 0.5
mA
· Wide frequency range
· Compact
IHC
Hysteresis offset current @ IP = 0,
after an excursion of IPN
± 0.6
mA
·
High immunity to external
IOT
Thermal drift of IO
0°C .. +70°C
± 0.03 mA/°C
< 3 µs
interference
tr
Response time @ 90% of IP
TCe
Thermal drift of the gain (% of reading)
< ± 0.04 %/°C
G
Applications
· DC motor drives
·
Switched Mode Power Supplies
(SMPS)
General data
TA
TS
RS
m
Ambient operating temperature
- 10 .. + 80 °C
- 15 .. + 85 °C
· AC variable speed drives
·
Ambient storage temperature
Secondary coil Resistance
Mass
Uninterruptible Power Supplies
(UPS)
Battery supplied applications
@TA = 25°C
30
W
·
310
g
· Inverters
010301/1
www.nanalem.co.jp