Current Transducer HNC-200P 200A-100mA IPN = 200 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Features
IPN
IP
VC
IC
Vd
RIS
IOUT
RL
Primary nominal r.m.s. current
Primary current, measuring range
Supply voltage (± 5 %)
200
A
A
V
mA
kV
MW
mA
W
± 400
± 15
± 15
2.5
> 500
100
· Hall effect measuring principle
· Galvanic isolation between primary
and secondary circuit
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
Isolation resistance @ 500 VDC
Output current @ ± IPN, RL = 10 kW, TA = 25°C
Load resistance
· Low power consumption
· Extended measuring range(3 x IPN
· Insulated plastic case recognized
according to UL 94-V0
)
40 .. 80
Accuracy-Dynamic performance data
Advantages
X
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error1) (0 .. ± IPN)
Electrical offset current, TA = 25°C
Hysteresis offset current @ IP = 0;
after an excursion of 1 x IPN
< ± 1 % of IPN
< ± 0.25% of IPN
· Easy mounting
e
· Small size and space saving
· Only one design for wide current
ratings range
· High immunity to external
interference.
L
IOE
IOH
< ± 0.5
mA
< ± 0.3 mA/K
< ± 0.005 mA/K
IOT
Thermal drift of IOE TA = -5..+70°C
TCe
Thermal drift of the gain (% of reading), TA = -5..+70°C < ± 0.04 %/K
Response time @ 90% of IP < 1 µs
G
tr
Applications
· DC motor drives
· Switched Mode Power Supplies
(SMPS)
· AC variable speed drives
· Uninterruptible Power Supplies
(UPS)
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 10 .. + 80 °C
- 15 .. + 85 °C
140
g
· Battery supplied applications
· Power supplies for welding
applications
Notes : 1) Linearity data exclude the electrical offset.
051013/0
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Page 1/2
LEM Industrial
www.lem.com