IPN = 50..600 A
Current Transducers HAS 50..600-P
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
VOUT = ± 4 V
Electrical data
Primarynominal
current rms
IPN (A)
Primary current,
measuring range
IPM (A)
Type
RoHS since
date code
50
± 150
± 300
± 600
± 900
± 900
± 900
± 900
HAS 50-P
46065
46062
planned
planned
46131
100
200
300
400
500
600
HAS 100-P
HAS 200-P
HAS 300-P
HAS 400-P
HAS 500-P
HAS 600-P
Features
· Hall effect measuring principle
· Galvanic isolation between primary
and secondary circuit
46216
planned
VC
IC
ÎP
Vd
Vb
RIS
VOUT
ROUT
RL
Supply voltage (± 5 %)
Current consumption
Overload capability
Rms voltage for AC isolation test, 50 Hz, 1 min
Rated isolation voltage rms, safe separation
Isolation resistance @ 500 VDC
± 15
± 15
30,000
3
5001)
> 1000
V
mA
At
kV
V
· Isolation voltage 3000 V~
· Low power consumption
· Extended measuring range (3 x IPN)
· Insulated plastic case made of
polycarbonate PBT recognized
according to UL 94-V0
MW
Output voltage (Analog)@ ± IPN, RL = 10 kW, TA = 25°C ± 4 V ± 40 mV
· Right angle pins for direct PCB
mounting
Output internal resistance
approx. 100
> 1
W
kW
6)
Load resistance
Advantages
Accuracy - Dynamic performance data
· Easy mounting
X
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error 2) (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0,
after an excursion of 1 x IPN
< ± 1
< ± 1 % of IPN
< ± 20
%
· Small size and space saving
· Only one design for wide current
ratings range
· High immunity to external
interference.
e
L
VOE
VOH
mV
< ± 20
< ± 2
< ± 1
< ± 0.1
< 3
mV
mV/K
mV/K
%/K
ms
TCVOE
Temperature coefficient of VOE HAS 50-P
HAS 100..600-P
Temperature coefficient of VOUT (% of reading)
Response time to 90% of IPN step
TCVOUT
tr
Applications
di/dt
BW
di/dt accurately followed
> 50
DC .. 50
A/ms
kHz
· AC variable speed drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies
(UPS)
· Switched Mode Power Supplies
(SMPS)
· Power supplies for welding
applications.
Frequency bandwidth (small signal, -3dB) 3) 4)
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
- 10 .. + 80 °C
- 25 .. + 85 °C
approx. 80 g
Mass
Standards
5)
EN 50082-2
1)
Notes : Pollution class 2, overvoltage category III.
2)
Linearity data exclude the electrical offset.
Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
Amorphous core option for high frequency application.
Please consult characterisation report for more technical details and
application advice.
3)
ApplicationDomain
· Industrial
4)
5)
6)
If the customer uses 1kW of the load resistor, the primary current has to
be limited as the nominal.
Page 1/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
061019/3
www.lem.com