Current Transducer HAL 50..600-S
For the electronic measurement of DC, AC and pulsed currents,
with a galvanic isolation between the primary (high power) circuit
and the secondary (electronic) circuit.
IPN = 50 A
Electrical data
Primarynominal
r.m.s. current
Primary current
measuring range
IP (A)
Type
I
PN (A)
Features
50
100
200
300
400
500
600
± 150
± 300
± 600
± 900
± 1000
± 1000
± 1000
HAL 50-S
HAL 100-S
HAL 200-S
HAL 300-S
HAL 400-S
HAL 500-S
HAL 600-S
· Open loop transducer using Hall
Effect
· Panel mounting - Horizontal or
Vertical
· Insulated plastic case to UL 94-V0.
ÎP
VOUT
RL
Overload capacity (Ampere Turns)
Analogue output voltage @ ± IPN
30000
± 4
> 1
> 3
± 15
25
500
3
> 500
A
V
kW
kW
V
mA
V
Advantages
Load resistance
TA = 0 .. + 70°C
TA = - 25 .. + 85°C
· Very good linearity
· Very good accuracy
VC
IC
Vb
Vd
Ris
Supply voltage (± 5%)
Current consumption (max)
Rms rated voltage1)
Rms voltage for AC isolation test, 50 Hz, 1 mn
Isolation resistance @ 500 VDC
· Low temperature drift
· Wide frequency bandwidth
· Very low insertion losses
· High immunity to external
interference
kV
MW
· Current overload capability
· Low power consumption
· Wide dynamic range, 50 to 600 A in
one package.
Accuracy - Dynamic performance data
X
e
Accuracy 2) @ IPN,TA = 25°C, @ ± 15 V
Linearity 2)
± 1
%
%
± 0.5
Max
± 10
L
VOE
VOM
Electrical offset voltage @ IP = 0, TA = 25°C
Residual offset voltage @ IP = 0
mV
Applications
after an overload of 3 x IPN
Thermal drift of offset voltage TA = - 25 .. + 85°C
± 10
± 2
± 0.05
< 3
> 50
mV
mV/°K
%/°K
µs
A/µs
kHz
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptable Power Supplies
(UPS)
VOT
TCe Thermal drift of gain TA = - 25 .. + 85°C
G
tr
Response time @ 90 % of IP
di/dt di/dt accurately followed
f
Frequency bandwidth (- 3 dB) 3)
DC .. 50
· Switched Mode Power Supplies
(SMPS)
General data
· Power supplies for welding
applications.
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 25 .. + 85
- 25 .. + 85
75
°C
°C
g
Standards Safety
EMC
EN50178 (1994)
EN50082-2 (1992)
EN50081-1 (1992)
Deviation in output when tested to EN 61000-4-6
Deviation in output when tested to EN 61000-4-4
< 10
< 10
% of IPN
% of IPN
Notes : 1) OvervoltageCategory III, Pollution Degree 2
001107/1
2)
Excludes the electrical offset
3) Refer to derating curves in the technical file to avoid excessive core
heating at high frequency
LEM Components