Voltage Transducer CV 4-4000
VPN = 2828 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
VPN
VP
VS
KN
RL
CL
VC
IC
Primary nominal r.m.s. voltage
Primary voltage, measuring range
Secondary analog voltage @ VP
Conversion ratio
Load resistance
Capacitive loading
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
2828
0 .. ± 4000
10
4000 V / 10 V
2
£ 5
± 15
V
V
V
Features
· Closed loop (compensated) voltage
transducer
· Insulated plastic case recognized
according to UL 94-V0
max
kW
nF
V
m A
k V
· Patent pending.
35 + VS / RL
9
Vd
Advantages
· Very good linearity
· Low thermal drift
· Low response time
· High bandwidth.
Accuracy - Dynamic performance data
Typ
Max
± 1
± 2
± 30
± 60
XG
VO
Overall accuracy @ VP max
Offset voltage @ VP = 0
TA = 25°C
- 25°C .. + 70°C
TA = 25°C
%
%
m V
m V
Applications
- 25°C .. + 70°C
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Uninterruptible Power Supplies
(UPS)
· Power supplies for welding
applications
· Railway overhead line voltage
measurement.
tr
f
Response time 1) @ 90 % of VPN
Frequency bandwidth (- 3 dB) @ 50 % of VPN
@ 25
DC .. 11
µs
kHz
General data
TA
TS
P
R1
m
Ambient operating temperature
Ambient storage temperature
Total primary power loss
Primary resistance
Mass
- 25 .. + 70
- 40 .. + 85
2.86
2.8
600
°C
°C
W
MW
g
Standards 2) 3)
EN 50155
EN 50178
1)
Notes : With a dv/dt of 1000 V/µs
2)
Specifications according to IEC 1000-4-3 are not guaranteed around
100 MHz. Sensitivity to induced radiation on connecting cable.
A list of corresponding tests is available.
3)
000613/2
LEM Components