5秒后页面跳转
APR50-B10 PDF预览

APR50-B10

更新时间: 2022-11-25 11:13:38
品牌 Logo 应用领域
莱姆 - LEM /
页数 文件大小 规格书
2页 59K
描述
AC Current transducer APR-B10

APR50-B10 数据手册

 浏览型号APR50-B10的Datasheet PDF文件第2页 
AC Current transducer APR-B10  
IPN = 10 .. 400 A  
Split core transducer for the electronic measurement distorted AC  
waveforms current, with galvanic isolation between the primary (High  
power)andthesecondarycircuits(Electroniccircuit).Switchselectable  
rangesandTrueRMS0-5Vand0-10Vswitchselectablevoltageoutput.  
Preliminary  
Electrical data  
Features  
Primary Nominal Current  
IPN (A.t.RMS)  
Analogue Output Signal  
VOUT (V)  
Type  
· VFD and SCR waveforms current  
measurement  
· True RMS output  
10,25,50  
0-5V or 0-10V  
0-5V or 0-10V  
0-5V or 0-10V  
0-5V or 0-10V  
APR 50 B10  
APR 100 B10  
APR 200 B10  
APR 400 B10  
· Split core type  
50,75,100  
100,150,200  
200,300,400  
· 5V & 10V switch selectable voltage  
output.  
· DIN mounting & Panel mounting  
· Eliminates insertion loss  
· Switch selectable ranges  
R L  
VC  
Vd  
Loadresistance  
Supplyvoltage  
³ 10  
+24±5% V DC  
kW  
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn  
Limitationofvoltageoutput  
5
18  
kV  
V
Advantages  
· Large aperture for cable up to Ø18mm  
· High isolation between primary and  
secondary circuits  
Accuracy-Dynamic performance data  
X
Accuracy @ IPN, TA = 25°C (without offset)  
< ±1  
% of IPN  
· Easy to mount  
e
Linearity (0 .. ± IPN)  
Electrical offset voltage, TA = 25°C  
Thermal drift of VOE  
Thermal drift of the gain (% of reading)  
Response time @ 90% of IP  
Frequencybandwidth(-3dB)  
< ±0.5 % of IPN  
< ±0.5 % of IPN  
VOLE  
VOT  
TCe  
t r  
Applications  
±1  
±0.1  
< 1000  
10 .. 6000  
mV/K  
%/K  
ms  
G
· VFD Controlled Loads:  
VFD output indicates how the motor  
and attached load are operating.  
· SCR Controlled Loads:  
f
Hz  
Acurate measurement of phase angle  
fired or burst fired (time proportioned)  
SCRs. Current measurement gives  
faster response than temperature  
measurement.  
General data  
TA  
TS  
m
Ambientoperatingtemperature  
Ambientstoragetemperature  
Mass  
Protectiontype  
ReliableisolationaccordingtoEN50178,EN61010 300  
Creepagedistance  
EMCinaccordancewithEN50082-2  
PlasticaccordingtoUL94V0, CTI1  
-20 .. +60  
-20 .. +85  
90  
°C  
°C  
g
· Switching Power Supplies and  
Electronic Ballasts:  
IP20  
VAC  
mm  
> 5.5  
True RMS sensing is the most  
accurate way to measure power  
supply or ballast input power.  
Notes : Installation and maintenance should be done with power supply disconnected.  
030708/0  
LEM Components  
www.lem.com  

与APR50-B10相关器件

型号 品牌 描述 获取价格 数据表
APR50B420L LEM AC Current transducer

获取价格

APR50-B420L LEM AC Current transducer APR-B420L

获取价格

APR6008 APLUS Voice Recording & Playback Device Voice Recording & Playback Device

获取价格

APR6008(28PDIP) APLUS Speech Synthesizer With RCDG, 480s, PDIP28

获取价格

APR6008(28SOP) APLUS Speech Synthesizer With RCDG, 480s, PDSO28

获取价格

APR6016 APLUS Voice Recording & Playback Device 16 Minute Duration

获取价格