5秒后页面跳转
AKR-C420L PDF预览

AKR-C420L

更新时间: 2022-04-23 23:00:11
品牌 Logo 应用领域
莱姆 - LEM /
页数 文件大小 规格书
2页 122K
描述
AC Current transducer

AKR-C420L 数据手册

 浏览型号AKR-C420L的Datasheet PDF文件第2页 
IPN = 2..200A  
AC Current transducer AKR-C420L  
Transducer for the electronic measurement AC waveforms current,  
with galvanic isolation between the primary (High power) and the  
secondary circuits (Electronic circuit). Jumper selectable ranges and  
True RMS 4-20mA current output.  
Electrical data  
Features  
Primary Nominal CurrentAnalogue Output Signal1)  
Type  
RoHS  
IPN (A.t.RMS)  
IOUT (mA)  
Date Code  
· VFD and SCR waveforms current  
measurement  
2,5  
4-20  
4-20  
4-20  
AKR 5 C420L JULY 2006  
AKR 50 C420L planned  
· True RMS responding  
· 4-20 mA Current output  
· Loop powered transducers  
· Panel mounting  
10,20,50  
100,150,200  
AKR 200 C420L JULY 2006  
Vc  
Supply voltage (Loop powered)  
24  
V DC  
· Accurate  
RL  
Vb  
Vd  
f
Load resistance  
see power supply diagram  
150  
· Jumper selectable ranges  
Rated voltage (CAT III, PD2)  
VAC  
kV AC  
Hz  
RMS Isolation voltage test, 50 Hz, 1mn  
Frequency bandwith  
3
Advantages  
20-100  
· Large aperture  
Accuracy - Dynamic performance data  
· High isolation between primary and  
secondary circuits  
· Easy to mount  
X
tr  
Accuracy@ IPN, TA=25°C  
± 1  
%
Response time @ 90% of IPN  
< 600  
mS  
Applications  
General data  
· VFD Controlled Loads:  
VFD output indicates how the motor  
and attached load are operating.  
TA  
TS  
m
Ambient operating temperature (0-95% RH)  
Ambient storage temperature  
-20 ..+ 50  
-20 ..+ 85  
°C  
°C  
g
· SCR Controlled Loads:  
Acurate measurement of phase  
angle fired or burst fired (time  
proportioned) SCRs.  
Mass  
Safety  
EMC  
90  
IEC 61010-1  
EN 61326  
· Switching Power Supplies and  
Electronic Ballasts:  
Note: 1) For 4-20mA output model, no saturation output up to 23 mA.  
True RMS sensing is the most  
accurate way to measure power  
supply or ballast input power.  
Selecting the transducer  
VFD (Variable Frequency Drive) and SCR (Semi Conductor Rectifier) output  
waveforms are rough approximations of a sine wave. There are numerous spikes  
and dips in each cycle. AKR transducers use a mathematical algorithm called  
“True RMS,” which integrates the actual waveform over time. True RMS is the only  
way to accurately measure distorted AC waveforms. Select AKR transducers for  
nonlinear loads or in “noisy” power environments.  
Options on request  
· DIN mounting  
060816/6  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.  
Page 1/2  
LEM  
www.lem.com  

与AKR-C420L相关器件

型号 品牌 描述 获取价格 数据表
AKS-0025 ETC Delay Line

获取价格

AKS-0025S ETC Delay Line

获取价格

AKS-0030 ETC Delay Line

获取价格

AKS-0030S ETC Delay Line

获取价格

AKS-0035 ETC Delay Line

获取价格

AKS-0035S ETC Delay Line

获取价格