AC Current transducer AK-C-
IPN = 10 .. 200 A
Transducerfortheelectronicmeasurementof ACsinusoidalwaveforms,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit). Jumper selectable ranges and
self powered transducers.
Electrical data
Primary Nominal Current
Analogue Output Signal1)
Type
RoHS
Date code
Features
IPN (A.t.RMS)
10,20,50
VOUT (V DC)
· AC sinusoïdal measurement
· Average responding
· Self powered transducers
· Panel mounting
5
AK 50 C5
AK 50 C10
AK 200 C5
planned
10,20,50
10
5
MAY 2006
planned
100,150,200
100,150,200
10
AK 200 C10 JUNE 2006
· Voltage output
· Jumper selectable ranges
Vc
RL
Vb
Vd
f
Supply voltage
Load resistance
Self Powered
1
MW
V AC
kV AC
Hz
Advantages
Rated voltage(CAT III, PD2)
RMS Isolation voltage test, 50 Hz, 1mn
Frequency bandwith
150
3
· Large aperture
50-60
· High isolation between primary and
secondary circuits
· Easy to mount
Accuracy - Dynamic performance data
X
tr
Accuracy @ IPN, TA=25°C
± 1
%
Applications
Response time @ 90% of IPN
< 100
mS
· Automation systems
Analog current reading for remote
monitoring (e.g. motor).
General data
· Data loggers
Self-powered transducer does not
drain data logger batteries.
TA
TS
m
Ambient operating temperature (0-95% RH)
Ambient storage temperature
- 20 ..+ 50
- 20 ..+ 85
°C
°C
g
· Panel meters
Simple connection displays power
consumption.
Mass
Safety
EMC
120
IEC 61010-1
EN 61326
Options on request
Note : 1) For 0-5 V output model, no saturation output up to 8.2 V
and for 0-10 V output model, no saturation output up to 15 V.
· DIN mounting
060816/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Page 1/2
LEM