Current Transducer LAS 100-TP
IPN = 100 A
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
16059
Electrical data
IPN
IP
Primary nominal r.m.s. current
Primary current, measuring range
at frequency > 1 kHz
100
0 .. ± 200
0 .. ± 300
A
A
A
Features
· Current transducer using
Eta-technology
VOUT
Analog output voltage @
IP
V
REF ±(0.625·IP/IPN) V
IP = 0
V REF ± 0.025
³ 2
< 20
V
kW
W
· Unipolar voltage supply
· Insulated plastic case recognized
according to UL 94-V0
RL
ROUT
Output load resistance
Output internal resistance
V REF Internal reference voltage
V REF load resistance
2.5 ± 0.025
³ 1
200
V
MW
W
· Compact design for PCB mounting
· Extended measuring range.
V REF internal resistance
VREF external voltage range
Max. output capacitive load
Supply voltage (± 5 %)
2.0 .. 2.8
1
5
18
V
nF
V
Advantages
CL
VC
IC
· Excellent accuracy
· Very good linearity
Current consumption @ VC = 5 V
typ
mA
· Very low temperature drift
· Optimized response time
· Wide frequency bandwidth
· No insertion losses
· High immunity to external
interference
Accuracy - Dynamic performance data
X
e
Accuracy 1) @ IPN , TA = 25°C
< ± 1
< 0.7
%
%
2)
Linearity error 0 .. IPN
L
Typ Max
· Current overload capability.
TCVOUT Thermal drift of VOUT @ IP = 0
TCVOUT /VREF Thermal drift of VOUT / VREF @ IP = 0 - 40°C .. + 85°C
- 40°C .. + 85°C
80 120 ppm/K
50 80 ppm/K
Applications
TCe Thermal drift of the gain
- 40°C .. + 85°C 300 500 ppm/K
G
VOM
tra
tr
Residual voltage@ IP = 0, after an overload of 2 x IPN DC ± 5
mV
ns
ns
· AC variable speed drives and servo
motor drives
Reaction time @ 10 % of IPN
Response time @ 90 % of IPN
di/dt di/dt accurately followed
< 200
< 500
> 100
< 10
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptible Power Supplies (UPS)
· Switched Mode Power Supplies (SMPS)
· Power supplies for welding
applications.
A/µs
mVpp
kHz
Output noise without external filter
f
Frequency bandwidth (- 1 dB)
DC .. 100
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 40 .. + 85
- 40 .. + 100
20
°C
°C
g
Application domain
· Industrial.
Standards
EN 50178 : 1997
All Data are given with a RL = 10 kW.
Copyright protected.
Notes : 1) Excluding electrical, magnetic offsets and linearity
2)
Including magnetic offset.
060303/6
page1/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM